10
ID-E299-001GB
•
with steady light – the disablement mode (line switch off),
•
no light – the quiescent (supervision) mode.
(3)
TRANSMISSION
– a red colour diode signalling - with continuous light – the general alarm relay
contacts switching in the active position.
(4)
FIRE
– a red colour display indicating a fire detection with flashing light (1 Hz frequency). The
indicator has the FIRE wording and is lit during the control panel alarm mode. The indication changes
for continuous light – after pressing the ACKNOWLEDGEMENT push button.
(5)
LCD display
– the displayed messages description is contained in p. 5.2.
(6)
POWER SUPPLY
– a green colour diode indicating that the control panel is connected to at least
mains or battery power supply.
(7)
DISABLEMENT
– a yellow colour diode signalling collectively disablement of:
•
at least one detection line,
•
signalling devices, or
•
alarm signal transmission (general alarm relays).
(8)
TESTING
– a yellow colour diode signalling the testing mode of at least one detection line;
(9)
FAULT
– a yellow colour diode indicating the fault mode (i.e. improper operation) of at least one
circuit being under the control panel supervision. Five additional yellow diodes described below
define which particular circuit is faulty.
(10)
POWER SUPPLY
– a yellow colour diode that signals:
•
with steady light – a battery fault,
•
with flashing light – mains fault.
(11)
SYSTEM
– a yellow colour diode signalling with steady light a fault in the microprocessor circuit
operation or a falsification of the configuration data.
(12)
EXTERNAL DEVICES
– a yellow colour diode that signals with steady light a fault of at least one
detection line.
(13)
SIGNALLING DEVICES
– a yellow colour diode indicating with steady light a fault of at least one
external signalling device.
(14)
EARTH FAULT
– a yellow colour diode signalling with steady light an earth fault of at least one
control panel circuit (connected with the earthing potential).
(15)
TRANSMISSION; OFF/ON
– a yellow colour diode placed near the push button that signals with
steady light the alarm relay disablement mode.
(16)
SIGNALLING DEVICES; OFF/ON
– a yellow colour diode placed near the push button indicates
with steady light the disablement mode of external signalling devices. The signalling devices can
operate only in the control panel fire alarm mode;
(17)
PERSONNEL; OFF/ON
– a yellow colour diode placed near the push button that signals with
steady light the control panel ‘PERSONNEL ABSENT’ mode.
(18)
ACKNOWLEDGEMENT
– a push button for acoustic signalling devices silencing and a fire alarm
receipt acknowledgement by the attending personnel; active at the 1
st
access level (without turning
the key).
(19)
RESET
– a push button for the control panel or detectors in detector lines fire alarm mode reset;
(20)
PERSONNEL ACCESS LEVEL
– a switch (a lock with a key) to actuate the handling elements
designed for usage at the 2
nd
access level (all push buttons placed on the front panel).
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...