- with the SELECTION and SET push buttons, choose the proper zone number and variant number
equal to ‘0’
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, set the proper delay time in minutes (0..9) – the X
position in the display and in seconds (00…59) – two following positions XX.
Note:
The delay value set is common for all zones.
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, choose the proper zone number and ‘1’ (on the last
display position) that results in the chosen zone delay disablement.
One-stage alarm with a preliminary reset
Programming:
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, choose the proper zone number (z. 01) and variant
number - ‘1’
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, choose the proper zone number and ‘0’ (on the last
display position) that results in the chosen zone delay disablement.
Two-stage alarm with a preliminary reset
Programming:
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, set the proper zone number and variant number
equal to ‘1’
- with the SELECTION and SET push buttons, set the proper delay time in minutes (0..9) – the X
position in the display and in seconds (00…59) – two following positions XX.
VARIANT z. 01 - 0
DELAY X’ XX’’
DELAYS ON z. 01 - 1
VARIANT z. 01 - 1
DELAYS ON z. 01 - 0
VARIANT z. 01 - 1
DELAY X’ XX’’
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...