14
ID-E299-001GB
zone number 1…16 or 24
0 – testing enabled
1 – testing disabled
TESTING ON z. 01 - 0
5.2.3 Zone disablement/re-enablement
A disablement/re-enablement of a zone (detection line) is possible using the following function:
zone number 1…16 or 24
0 – zone enabled
1 – zone disabled
ZONE ON z. 01 - 0
5.2.4 Faults readout
In order to read the faults out, it is necessary to select with the FUNCTION push button the following
indication on the display:
Afterwards, using the SET^ push bu[on recall the messages informing on the current faults
registered in the system.
The below table lists the possible faults with their clarifications.
BZ3 FUSE FAULT
BZ3 fuse fault
BATT.VOLTAGE DECR.
Battery voltage drop
MAINS POW.SUP.FAULT
230 V mains power supply fault
BATTERY FAULT
Battery cluster or its circuit fault
EARTH FAULT
Damage of insulation between control panel and
grounding
LACK OF CHARGING
Charging circuit fault of interruption
SYSTEM FAULT
Control panel controller program execution
disruption
FAULT READOUT
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...