18
ID-E299-001GB
5.3.5 ‘Standard configuration’ loading
0 – loading function disabled
1 – loading function enabled
STAND. CONF. - 0
Note:
The Standard configuration loading is possible after the loading function initiation with the SET^
push button and pressing the (P13) RESET push button.
5.3.6 Alarm variants programming
zone number 1…16 or 24
1 – alarm variant number
(0, 1 or 2)
VARIANT z. 01 - 1
The setting change - with the SET^ and SET` push bu[ons.
Note:
The variant 2 (zone interdependence) loading takes place automatically in both detection lines
constituting the interdependent pair.
One-stage alarm
Programming:
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, choose the proper zone number and variant number
equal to ‘0’
- using the FUNCTION push button, select the function
- with the SELECTION and SET push buttons, choose the proper zone number and ‘0’ (on the last
display position) that results in the chosen zone delay disablement.
Two-stage alarm
Programming:
- using the FUNCTION push button, select the function
VARIANT z. 01 - 0
DELAYS ON z. 01 - 0