ID-E299-001GB
21
-
In case another pair of interdependent zones should be formed, it is necessary to change places of
the detector lines connection on the clamp board.
Two-stage alarm with zone-time interdependence
The control panel operation is same as in the preceding alarm variant with one exception: a 1
st
stage
alarm is omitted and a 2
nd
stage alarm is evoked immediately.
In the programming process it is necessary to repeat the operations from the preceding description
with the exception of the ‘delay on’ function, where the particular zone delay should be disabled as
shown below:
5.3.7 Zone relay programming
12 – zone number 1…16 or 24
- -
no relay assigned
or ‘RES’ reset – relays act
- -
no relay assigned
only during alarm reset
*
-
number of relay assigned to reset function
12 – number of zone relay 0…16 (24)
12 P: 12 * - -
The function enables:
- to assign to each of 16 (24) zones 0…4 zone relays that will switch the contacts over when a
given zone enters the alarm mode; the same relay can be assigned to different zones; the
contacts return to the rest position takes place after the control panel alarm mode reset;
- to program 0…4 zone relays actuation is such the manner that the contacts switchover takes
place during the alarm mode reset and this relay actuation is not dependent on the alarm
mode and reset.
Appearance of ‘*’ instead of a relay number means that this relay has already been assigned to the
reset function.
Example 1:
The above setting means that in the alarm mode of the fourth zone, the relays marked as 4, 16 and
20 will be actuated.
The above setting means that during the control panel alarm mode reset, the contacts marked as 1
and 17 will be switched over. After a reset the contacts return to the previous position.
DELAYS ON z. 01 - 0
04 P: 4 16 20
RES P: 1 17 - -
Summary of Contents for Ignis 1000
Page 37: ...ID E299 001GB 37 Fig 1 Control panel front side view ...
Page 38: ...38 ID E299 001GB Fig 2 IGNIS 1240 design and dimensions ...
Page 39: ...ID E299 001GB 39 Fig 3 Control panel mounting ...
Page 41: ...ID E299 001GB 41 Fig 6 Control panel Power supply unit view ...
Page 43: ...ID E299 001GB 43 Fig 8 G 35 base connection method into detection line ...
Page 44: ...44 ID E299 001GB Fig 9 G 40 base connection method into detection line ...