Copyright Planika Sp. z o.o.
www.planikafires.com
IG0058#00
31.03.2017
25
The error code can be reset by simultaneous pressing the buttons
and
on the remote control (when the device is not permanently locked,
eg. following repeated ignition attempts). The error code will disappear and it will be
possible to restart the device. WARNING! You cannot use the device if the fault is
repeated. Please contact your installer.
In the case of an error message F01 or F08 you can reset and try to turn the device on up to 3 times in a row. If ignition
fails, F00 error appears on the display and ignition is not possible for another 30-minutes.
ERROR
CODE
FAULT
POSSIBLE CAUSE
REPAIR
SMELL OF GAS
IMMEDIATELY CLOSE THE GAS VALVE ON THE GAS CONNECTION. DO
NOT USE THE APPLIANCE UNTIL SPILLS ARE FULLY REMOVED
F01
The lack of
communication
between the receiver
and the automation
controller
Communication cable does not
make any contact
Make sure that the contacts of the
communication cable ensure correct
contact
Damage to the communication
cable
Replace the communication cable
F02
Overheating of the
receiver (60 ° c above
room temperature)
Poor ventilation by the receiver Improve ventilation at the receiver
The receiver is in contact with
the hot parts
Move the receiver so that it does not
touch the hot parts
F03
Internal NTC sensor(
of the receiver) is not
working properly
Damaged receiver
Replace Receiver
F04
External NTC sensor is
not working properly
External NTC sensor or wiring
are damaged
Replace the NTC sensor or wiring
F05
Internal security error Damaged receiver
Replace Receiver
F06
Lack of
communication
between the
transmitter and
receiver
The transmitter is out of range
of the receiver
Make sure that the transmitter is
located near the receiver
Any obstacles between the
transmitter and the receiver
may interfere with the signal
Remove any obstacles between the
transmitter and receiver
Power transmission is too weak Check the power transmission (see.
Instruction Manual Chapter 9)