Wiring
Operating Manual PSEN sg2c-5CCLLE
1004172-EN-02
| 21
}
When calculating the max. cable run, remember to take into account the chapter "Notes
on cable run".
5.4
Terminal configuration
1
X2
3
5
7
9 11 13 15
2
4
6
8 10 12 14 16
1
X1
3
5
7
9 11 13 15
2
4
6
8 10 12 14 16
Terminal
PSEN sg2c-5CCLLE
X1-1 - X2-1
linked internally
+24 VDC supply voltage
X1-2 - X2-2
linked internally
0 V
X1-3
Safety output channel 1 (OSSD1)
X1-4
Safety output channel 2 (OSSD2)
X1-6 - X2-6
linked internally
Solenoid operation (24 V)
X1-7 - X2-7
linked internally
Solenoid operation (24 V)
X1-8 - X2-8
linked internally
Input for activating the safety gate guard
locking device
X1-9
Signal output for state of the bolt tongue
X1-10
E-STOP 1.1
X1-11
E-STOP 1.2
X1-12
E-STOP 2.1
X1-13
E-STOP 2.2
X1-14
Pushbutton 3 LED3
X1-15
Pushbutton 4 LED4
X1-16
Signal output, E-STOP
X2-3
Input, channel 1
X2-4
Input, channel 2
X2-13
Pushbutton 3 channel 1
X2-15
Pushbutton 4 channel 1