Function description
Operating Manual PSEN op2B/1 Series
1003357-EN-02
14
4.1.1
Function settings when delivered
The safety light grid
is delivered with all DIP switches in the ON position.
1
2
3
4
5
6
7
8
ON
Fig.: DIP switches all ON
As a result the functions are set as follows:
Function
DIP switch
Position
Set function
Timeout muting
1 and 5
ON
10 minutes
Muting
2 and 6
ON
T-configuration (4 beams) or
cross muting
When using the L-configuration,
DIP switches 2 and 6 must be set
to OFF.
EDM
3 and 7
ON
Deactivated
Restart interlock
4 and 8
ON
Without restart interlock
Functions can be selected via DIP switch - settings when delivered
4.2
Restart after unit is triggered
If the safety light grid
has switched off the OSSDs, the connected machine is stopped.
Once the protected field is clear again, the safety light grid
must be reset to its normal oper-
ating state.
The restart can be achieved in two ways:
}
Without restart interlock (status when delivered)
The safety light grid is automatically reset to its normal operating state.
}
With restart interlock
The light grid is not reset to its normal operating state until
– The TEST/START button has been operated for at least 0.5 s and
– The area of the protected field is clear again and the light beams are no longer in-
terrupted.
NOTICE
The machine may only be restarted via a TEST/START button.
It must not be possible to operate the pushbutton from inside the danger
zone. The button must be located at a position from which there is a full, un-
obstructed view of the danger zone.