GW EIP/ASCII...
72
PHOENIX CONTACT
3785_en_B
Output assembly instances:
Output assembly instances are grouped into one continuous
array. One or more output instances may be written to with one connection. The write may
begin at any instance from 109 to 116, and the length of the write may range from the length
of the initial output instance or up to the total length of the remaining output instances. For
example, the write may begin at output instance 109 and be the length of output instance
109, or begin at instance 109 with a length of output instances 109, 110, 111, 112, 113, 114,
115, and 116. Only one controller may access the output assembly instance at a time.
Table 5-42
Output assembly instance attributes
Assembly
instance number
Name
Data type
Data value
Access rule
109
Transmit data to serial
ports 1 to 4
Transmit data to socket
ports 1 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
110
Transmit data to serial
ports 2 to 4
Transmit data to socket
ports 1 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
111
Transmit data to serial
ports 3 to 4
Transmit data to socket
ports 1 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
112
Transmit data to serial port
4
Transmit data to socket
ports 1 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
113
Transmit data to socket
ports 1 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
114
Transmit data to socket
ports 2 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
115
Transmit data to socket
ports 3 to 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set
116
Transmit data to socket
port 4
BYTE array length = (4 +
maximum RX packet size)
0 - 255
Set