Ordering data and technical data
110146_en_00
PHOENIX CONTACT
117 / 128
Conformance with EMC Directive 2014/30/EU
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/
IEC 61000-4-2
Criterion B, 6 kV contact discharge, 8 kV air discharge
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
Criterion A, Field intensity: 10 V/m
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV
Transient overvoltage (surge) EN 61000-4-5/
IEC 61000-4-5
Criterion B, supply lines: 0.5 kV, signal/data cables: 1 kV
Conducted interference EN 61000-4-6/IEC 61000-4-6
Criterion A, Test voltage 10 V
Noise emission test in accordance with
EN 61000-6-4/IEC 61000-6-4
This is a Class A item of equipment. When using the equipment in residential areas, it may cause radio inter
-
ference. In this case, the operator may be required to implement appropriate measures and to pay the resulting
costs.