SAMPLING TIME 1 (S)
The set value is the minimum measuring time (for channel A) in seconds. The
sampling time acts as a filter for irregular frequencies. This parameter directly
affects the reaction time of the device.
Value
Function
0.001
Minimum measuring time in seconds
0.1
Default value
9.999
Maximum measuring time in seconds
WAIT TIME 1 (S)
The set value is the zero setting time. This parameter defines the duration
of the lowest frequency, or the waiting time between two rising edges on
channel A, at which the device detects the 0 Hz frequency. Frequencies
with a duration greater than the set WAIT TIME 1 are evaluated as
frequency = 0 Hz.
Value
Function
0.01
Frequency = 0 Hz for frequencies less than 100 Hz
1.00
Default value
79.99
Frequency = 0 Hz for frequencies less than ~ 0.01 Hz