O
PERATING
S
OFTWARE
OS6.0
/
OS10.0
44
OUTPUT POLARITY 1
Switch state for the switch condition of preselection 1.
Value Designation
Function
0
ACTIVE HIGH
Active "HIGH"
1
ACTIVE LOW
Active "LOW"
OUTPUT LOCK 1
Self-locking for the switch condition of preselection 1.
Value Designation
Function
0
NO
No self-locking
1
YES
Self-locking
STARTUP DELAY 1 (S)
Startup override for the switch condition of preselection 1.
Time frame until the monitoring function is focused.
This setting only applies for switch conditions |RESULT|<=|PRES| or
RESULT<=PRES and only for operating mode "FREQUENCY" MODE – channel
A.
STARTUP DELAY is set at a frequency of 0 Hz to the parameter set here and
started. The monitoring function remains deactivated until the set time has
elapsed.
A setting of "60,000" activates automatic startup override. This means that the
monitoring function remains deactivated until the preselection value / switch point
is exceeded for the first time.
Value
Function
0.000
No startup override
…
59,999
Startup override in seconds
60,000
Automatic startup override