Connection of the RS422 signals
DPI measurement mode:
In managing operation, the init pulse is sent at regular intervals (=SAMPLING
TIME [ms]) on the init line to the displacement transducer, the rising edge of
which triggers a measurement.
The pulse duration of the init pulse can be set using the "INIT pulse TIME (µs)"
parameter.
T
Init
:
1
µ
s … 9
µ
s (adjustable)
T
Start
:
~3
µ
s … 5
µ
s
T
Stop
:
~3
µ
s … 5
µ
s
3.6
Control Inputs (X5)
Six control inputs with HTL-PNP characteristics are available at terminal X5 pins
2, 3, 4, 5, 6, and 7.
Control input 1 (Ctrl. In 1) to control input 5 (Ctrl. In 5) are freely configurable in
the COMMAND menu and are used for externally triggered functions such as
releasing the self-locking mechanism, resetting the measurement result, or for