Heat Pump Installation and User’s Guide

2

 

ULTRATEMP

®  

Heat Pump Installation and User’s Guide 

Heat Pump Dimensions

38.7"

(983 mm)

4.5"

(114 mm)

9.25"

(235 mm)

11.25"

(286 mm)

A

34.0"

(864 mm)

32.0"

(813 mm)

30.7"

(780 mm)

INSTALLATION AND LOCATION

When pool equipment is located below the pool surface, a leak from any component can cause large scale water loss or flooding. 
Pentair Water Pool and Spa, Inc. cannot be responsible for such water loss or flooding which may cause damage to the product. 
Avoid placing the heat pump in locations where it can cause damage by water or condensate leakage. If this is not possible, provide 
a suitable drain pan to catch and divert any leakage. 

Equipment Pad
For proper drainage of condensation and rain water, 
place the heat pump on a flat slightly pitched surface, 
such as a concrete or fabricated slab (pad). 
If possible, place the pad at the same level or slightly 
higher than the filter system equipment pad.

Note: 

Be sure that the pad is pitched not more than 1/4 

in. per foot in any direction as needed for runoff.

Drainage and Condensation
Condensation occurs from the evaporator coil while the 
unit is running, and drains at a steady rate (usually three 
to five gallons per hour), depending upon ambient air 
temperature and humidity. The more humid the ambient 
conditions, the more condensation will be produced. 
The bottom of the unit acts as a tray to catch rainwater 
and condensation. Keep the drain holes, located on the 
bottom pan of the base of the unit, clear of debris. 

Roof Run-off
Make sure the heat pump is not located where large 
amounts of water may run-off from a roof into the unit.
Sharp sloping roofs without gutters will allow massive 
amounts of rain water, mixed with debris from the roof 
to be forced through the unit. A gutter or down spout 
may be needed to protect the heat pump.

MODELS

DIMENSION “A”

 

70, 90, 90l

33.5” (851 mm)

100l

41.5” (1054 mm)

110, 120, 120C, 140C

120 H/C, 140, 140 H/C

45.5” (1156 mm)

Lawn Sprinklers
Avoid placing lawn sprinkler near the heater - 
they can spray water into the heater and void the 
warranty.

 

Be sure to direct any spraying water away 

from the heater. Note the wind direction to be sure 
water from sprinklers is not blown toward the heater. 
Sprinkler heads can produce high water pressure and 
spray at an angle, different from typical rain and humid 
weather. Also, sprinklers connected to a well water 
system can cause mineral build up on the evaporator 
coils and electronics. Salt water can also be an issue if 
located near the coast.

Only a qualified service person should install the 
UltraTemp

®

 Heat Pump. Before installing this product, 

refer to the Important Warning and Safety Instructions 
on page ii.

1.  Plumbing connections (2 inch). 
2.  Level surface for proper drainage. 
3.  Suitable electrical supply line. See rating plate on 

unit for electrical specifications. A junction box is not 
needed at the heat pump; connections are made 
inside of the heat pump electrical compartment. 
Conduit may be attached directly to the heat pump 
jacket.  

4.  Electric cutout switch that will interrupt all power to 

the unit. This switch must be within line of sight of 
the heat pump. Check local codes for requirements.  

5.  Watertight conduit to run the electrical supply line.

Materials Needed for Installation
The following items are needed and are to be supplied 
by the installer for all heat pump installations: 

Summary of Contents for ULTRATEMP

Page 1: ...INSTALLATION AND USER S GUIDE HEAT PUMP IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS ULTRATEMP...

Page 2: ...ecting to an Automation System Remote Operation Relay Remote Controls Connecting to IntelliTouch or EasyTouch via Heat Pump Spade Terminals Connecting to IntelliTouch or EasyTouch via RS 485 Connector...

Page 3: ...8 C is considered safe for a healthy adult Special caution is suggested for young children Prolonged immersion in hot water can induce hyperthermia 2 Drinking of alcoholic beverages before or during s...

Page 4: ...ISH ESPANOL SOFTWARE VERSION REV ____ PUMP START TIME TIME 1 4 HRS INTELL ADDRESS ADDRESS 1 16 TEMPERATURE SCALE FAHRENHEIT CELSIUS PRESS POOL SPA TO EXIT SETUP WP HP LP PL SP 1 1 1 0 0 FAN COMP PMP R...

Page 5: ...rce and provide a dual electronic thermostat control system for pool spa combinations or preheat convenience 3 This heat pump is specifically designed for heating fresh water swimming pools and spas D...

Page 6: ...a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or down spout may be needed to...

Page 7: ...water 4 Install heat pump a minimum of 6 in 153 mm from the wall of the house Anchor Clamp Installation Installation of the anchor clamps is recommended in all installations Installation of the ancho...

Page 8: ...t below the pool water surface See instructions for pressure switch adjustment on the next page If the heat pump is installed outside of this range an external pressure switch may need to be installed...

Page 9: ...clean before making any pressure switch adjustment A dirty filter will restrict the water flow and the pressure switch cannot be adjusted properly To adjust the pressure switch The following adjustme...

Page 10: ...switch is located in the water plumbing in the lower right corner of the heat pump 5 Slowly rotate the adjustment wheel on the water pressure switch in a counterclockwise direction until the LOW WATE...

Page 11: ...um 24 610 mm 153 mm 12 305 mm 4 610 mm min earance for ervice access 153 mm 6 6 Multiple Unit Installation Extend 12 305 mm past end heater inlet for hydraulic balancing Extend 12 305 mm past end heat...

Page 12: ...the power to the circuit for the heat pump is turned off 1 Remove the front left panel of the heat pump cabinet you do not need to remove the torque head screw at the top left corner 2 Remove the ser...

Page 13: ...N P U M P COM SPA POOL INPUT SWITCHES J9 WTR TEMP J4 DEF TEMP J5 3 WIRE REMOTE TERM PWR J7 RS 485 J8 INTELLITOUCH CONNECTION BLACK OUTPUTS J3 BLACK WHITE PURPLE BLACK BLACK Capacitor COMPR FAN FAN HER...

Page 14: ...ion Device GRAY ORANGE BLACK RED YELLOW GREEN YELLOW BLUE RED GRAY T H E R M 1 T H E R M 2 GREEN C Note If red LED is on swap any two phases Label P N 474022 Rev B Compressor R C S 24 VAC C O M P R E...

Page 15: ...3 WIRE REMOTE TERM PWR J7 J8 CONNECTION BLACK OUTPUTS J3 BLACK PURPLE BLACK BLACK Transformer 415V 24 VAC COM Compressor Contactor Fan Relay BLACK WHITE BLACK BLUE BLUE WHITE PURPLE ORANGE BLACK YELL...

Page 16: ...ipment to the heat pump perform the following steps 1 Turnoffthepowertoboththeremotepool spacontrol system and the heat pump 2 Remove the front left panel of the heat pump cabinet you do not need to r...

Page 17: ...nections 2 Unlatch the front door spring latches and open the front door of the IntelliTouch or EasyTouch Load Center 3 Loosen the two retaining screws from the top of the control panel and lower the...

Page 18: ...a the optional four wire cable P N 520199 To connect the heat pump board cable to the IntelliTouch or EasyTouch load center 1 Unlatch the IntelliTouch or EasyTouch load center front door spring latche...

Page 19: ...Pin Configuration for the Heat Pump Control Board to IntelliTouch Control System 1 Heat Pump Control Board Connect pin 2 green to IntelliTouch screw terminal pin 2 green 2 Heat Pump Control Board Conn...

Page 20: ...WN arrows 4 UP and DOWN Arrow buttons The UP and DOWN arrows will raise or lower the temperature set point if pressed while the run screen is displayed They are also used to scroll through the various...

Page 21: ...evision Displays the software revision level loaded on the control board 3 Pump Start Time This displays the period at which the heat pump will close the AutoSet contactor to start the filter pump Adj...

Page 22: ...l become active TEMPERATURE SCALE FAHRENHEIT CELSIUS TEMP OFFSET OFFSET 2 TO 2 Defrost Cycle The UltraTemp Heat Pump may enter a defrost cycle if air temperatures are around 50 F 10 C The defrost cycl...

Page 23: ...ch allows the heat pump to heat or cool the water as necessary 6 Time Delay Screen If the heat pump is waiting on any restart pump start or sensing water temperature delays this screen shows how much...

Page 24: ...During the selected time frame the green LED indicator is on and the heat pump functions in the normal mode of operation When the green led indicator turns off the heat pump turns off when time expire...

Page 25: ...OWN arrows to toggle between the ON and OFF options AutoSet Enable this feature any time the filter pump is off The AutoSet feature periodically energizes a contactor which can be connected to the pum...

Page 26: ...s a protection feature for the heat pump s compressor This extends the life of the compressor s by not allowing it to cycle on and off i e adjusting set point up and down around actual temperature Cou...

Page 27: ...mp has been winterized perform the following steps when starting the system in the Spring 1 Uncovertheheatpumpandinspectthetopandsides for any debris or structural problems 2 Connect the water inlet a...

Page 28: ...while in operation The heat pump base is designed to allow the condensation to exit through the bottom drain port when the unit is running The condensation will increase as the outdoor air humidity l...

Page 29: ...6 7 6 8 6 4 5 1 4 4 32 2 34 87 3 90 6 2 5 4 4 19 NA NA 4 9 4 1 4 2 5 3 6 6 5 9 140 140 H C 208 230 3 60 208 230 1 60 43 43 50 50 70 70 32 3 35 32 3 35 185 11 196 185 11 196 50 NA NA 50 NA NA 140 000 1...

Page 30: ...UltraTemp 140 352 168 12 UltraTemp 140 325 98 3 UltraTemp 140 H C 377 170 10 UltraTemp 140 H C 327 100 3 UltraTemp 120C 354 150 12 UltraTemp 120C 318 89 4 UltraTemp 140C 365 168 13 UltraTemp 140C 320...

Page 31: ...ature sensor circuit is shorted Bad Thermistor or bad control board Use the 10k ohm resistance test to verify thermistor If shows shorted replace thermistor If good replace control board SUCTION TH OP...

Page 32: ...n entire filtering system and or replace filter element Inspect clean pump impeller Adjust all plumbing valves Repair suction air leaks grease pump lid O ring Replace filter Wrong filter pump pipe siz...

Page 33: ...ure switch Check Alarm Status on Control Board for LOW REFRIG Alarm The outside air temperature too low and Defrost feature is NOT enable Malfunctioning Defrost Thermistor Make sure heater is installe...

Page 34: ...ufficient water flow system overcharged See Possible Cause column for TXV stuck closed Insuf ficient water flow and Unit overcharged Low current with high superheat Unit undercharged Find source of re...

Page 35: ...40 32 13 3 26 6 29 30 12 31 33 34 28 5 15 14 43 11 44 7 10 35 36 9 8 38 39 24 25 25 25 2 41 42 4 27 37 1 B DETAIL B Single Phase DETAIL B Three Phase 19 20 21 22 18 16 17 23 SEE DETAIL B 19 18 17 21...