MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
52
Revision Level 002
9.13. MAC
ADDRESS
(BACNET COMMUNICATION OPTION)
When the BACnet Communication option is ordered, the MAC Address Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 02. For additional
information refer to the Communication O&M.
Tech. Config.
Password: 1000
Cont. Output Menu
MAC Address
Correction Coeff.
4PT Flow Corr
(Range = 02 to 254)
MAC Address
(002)
Instance Number
Modbus ID
Baud Rate
9.14. INSTANCE NUMBER (BACNET COMMUNICATION OPTION)
When the BACnet Communication option is ordered, the Instance Number Menu allows the user to set a
unique device address when connecting to a BACnet network. The default is 1002. For additional
information refer to the Communication O&M.
Tech. Config.
Password: 1000
Cont. Output Menu
Instance Number
Correction Coeff.
4PT Flow Corr
(Default = 1002)
MAC Address
(01002)
Instance Number
Modbus ID
Baud Rate