8.7.4. Fixed
Value
The Fixed Value Menu allows the user to enter a temperature value other than the standard value of 68
˚
F
for the flow calculations. This value will not be displayed on the LCD screen.
Field
Setup
Menu
Operating Range
Temp. Comp.
Fixed Value
Zero Calibration
Temp. Units
Eng. Units
Temp. Values
(
F)
Lockdown
Temp
Input
(+068)
Flow Correction
Fixed Value
Auto Zero
Temp. Comp.
Meas. Fl. Disp. Fltr
8.8.
MEASURED FLOW DISPLAY FILTER
The Measured Flow Display Filter Menu allows the user to vary the Measured Flow Display Filter
rolling average Sample Interval Time from 00.1 to 65.5 seconds and the Sample Count from 0 to 150.
The Measured Flow Display Filter is independent of the Process Output Filter Value (see Section 8.9).
Field Setup
Menu
Operating Range
Measured Flow Filter
Zero Calibration
Eng. Units
Sample Interval Time
Lockdown
(00.5)
sec
Flow Correction
Auto Zero
Sample Count
Temp. Comp.
(0-150)
Meas. Fl. Disp. Fltr
(010)