Summing Operation & Maintenance Manual
Paragon Controls Incorporated
26
Revision Level 002
8.7.1. Temperature
Units
The Temperature Units Menu allows the user to select the appropriate temperature units for the job.
Field
Setup
Menu
Operating Range
Temp. Comp.
Temp. Units
Zero Calibration
Temp. Units
Eng. Units
Temp. Values
°
F/
°
C
Lockdown
Temp
Input
Flow Correction
Fixed Value
(
°
F)
Auto Zero
Temp. Comp.
Meas. Fl. Disp. Fltr
8.7.2. Temperature
Values
The Temperature Values Menu allows the factory or user to set the minimum and maximum temperature
range values that represent the input signal from the external temperature transmitter or the building
automation system.
Field
Setup
Menu
Operating Range
Temp. Comp.
Temp. Range
Zero Calibration
Temp. Units
Eng. Units
Temp. Values
Min
Value
Lockdown
Temp
Input
(-030)
Flow Correction
Fixed Value
Auto Zero
Max Value
Temp. Comp.
(130)
Meas. Fl. Disp. Fltr
If the new temperature values cause the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
See Temperature Range Example below.
Warning Message:
Op Range Outside
Allowable Value
Op Range will be
Reset to the MAX
F.S. Value
(Press Enter)