Summing Operation & Maintenance Manual
Paragon Controls Incorporated
41
Revision Level 002
9.3.3. Span Calibration
The Span Calibration Menu allows the user to perform a span transducer calibration to eliminate any
possible transducer drift. This value will be placed in a different memory location than the Factory Span
memory location and used until a Return to Factory Defaults is selected (see Section 8.12).
Tech Config
Password: 1000
Controller Parameters
Min. Calibration
Input Value
CPU
Taking
Area Factor
50% Calibration
(+0.1000) inch w.c.
Samples
Transducer Cal.
Span Calibration
Ext. Flow Source
Return to Menu
(Press ENTER)
(Please Wait)
Ext. Flow Span
Altitude
Process Output Menu
Temp. Output Menu
9.4.
TEMPERATURE FIXED VALUE (NO TEMP COMP OPTION)
When the Temperature Compensation option (see Section 8.7) is not ordered, the Temperature Fixed
Value Menu allows the user to enter a temperature value other than the standard value of 68
˚
F for the
density calculations. This value will not be displayed on the LCD screen.
Tech. Config.
Password: 1000
Controller Parameters
Temp Fixed Value
Area Factor
Transducer Cal.
(°F)
Temp Fixed Value
Ext. Flow Source
(+068)
Ext. Flow Span
Altitude
Process Output Cal.