MicroTrans
II
Summing Operation & Maintenance Manual
Paragon Controls Incorporated
48
Revision Level 002
9.10. CONTROLLER OUTPUT MENU
9.10.1. Voltage Output Level Selection
The Voltage Output Level Selection Menu allows the user to select either 0-5VDC or 0-10VDC for the
Temperature Output voltage signal. See Section 4.6 for switch selection.
Tech Config
Password: 1000
Cont. Output Menu
Volt Out 5/10vdc
Volt Out 5/10vdc
Correction Coeff.
Min Calibration
4PT Flow Corr
Span
Calibration
(0-5V / 0-10V)
MAC Address
Return to Menu
Instance Number
(05) Volt
Modbus ID
Baud Rate
9.10.2. Minimum Calibration
The Minimum Calibration Menu allows the user to make output zero adjustments. Monitor the output
and with each Up or Down button depression, the output will increase or decrease by 0.01VDC or
0.01mA depending on output selection.
Tech Config
Password: 1000
Cont. Output Menu
Volt Out 5/10vdc
Use Up/Down
Correction Coeff.
Min Calibration
Buttons
4PT Flow Corr
Span
Calibration
To Adjust Output
MAC Address
Return to Menu
(Press Enter)
Instance Number
Modbus ID
Baud Rate