Summing Operation & Maintenance Manual
Paragon Controls Incorporated
43
Revision Level 002
9.7. ALTITUDE
The Altitude Menu allows user to enter the specific altitude for the job other than the standard value of 0
feet above mean sea level for the density calculations.
Tech. Config.
Password: 1000
Controller Parameters
Altitude
Area Factor
Transducer Cal.
(0000)Ft
Ext. Flow Source
Ext. Flow Span
Altitude
Process Output Menu
Temp. Output Menu
If the new Altitude causes the existing Operating Range Value to be outside the new calculated
Minimum or Maximum Full Scale Value, the below Warning Message will appear and the Operating
Range will be reset to the new Maximum Full Scale Value by pressing Enter. The display will
automatically jump to the Op Range Menu allowing the user to enter a new Operating Range Value.
This can be accomplished by performing the steps under Section 5.2. See Altitude Example below.
Warning Message:
Op Range Outside
Allowable Value
Op Range will be
Reset to the MAX
F.S. Value
(Press Enter)