54
Fig.16. Operation of the analog output when overflow manage
-
ment is switched on
Temperature [
o
C]
Analog output [mA]
Example 2: Configuration of the analog output controlled by real time clock
The transducer set to measure temperature form Thermocouple J:
Therm.J 0..400
o
C
. The individual characteristic of the current
type analog output is set, that the output reacts to current time (hour,
minute), i.e. for 00:00 o’clock expected value is 4 mA, for 23:59 o’clock
expected value is 20 mA:
Table 14
Register no.
Parameter
symbol
in the menu
Register value
Parameter value
symbol
in the menu
4040
Param.An
0
Time
4041
OverServ
1
Off
7610
AnIn Lo
0
0.0
7611
AnIn Hi
23.59
23.59
7612
AnOut Lo
4
4
7613
AnOut Hi
20
20.0