5.5.2.2. Analog output overflow management
In PCE-P30U transducer user can additionally configure
the behaviour of the analog output after controlling output value over-
flow. By default, overflow management is switched off – in such a case,
after controlling output value is overflowed, the output is still controlled
proportionally to the controlling output value outside the basic range
of the output. After the overflow management is switched on,
the user can define the value to control the output after the occurrence
of the upper or lower overflow of the controlling output value.
Example 1: Analog output configuration
The transducer set to measure temperature from
thermocouple J – Input:
Therm.J -200..1200
o
C
. Individual
characteristic of the current type analog output set as follows:
Fig.14. Analog output individual characteristic