39
Status Register 2 – reactive power characteristics
(address 4051, R):
Bit 15...12 - reserved
Bit 11 – „1” – capacity 3L max,
Bit 10 – „1” – capacity 3L min.
Bit 9 – „1” – capacity 3L
Bit 8 – „1” – capacity L3 max.
Bit 7 – „1” – capacity L3 min.
Bit 6 – „1” – capacity L3
Bit 5 – „1” – capacity L2 max.
Bit 4 – „1” – capacity L2 min.
Bit 3 – „1” – capacity L2
Bit 2 – „1” – capacity L1 max.
Bit 1 – „1” – capacity L1 min.
Bit 0 – „1” – capacity L1
Configuration register of displayed base quantities parameters
(address 4056, R/W):
Bit 15 – „1” – date and time display
Bit 14 – „1” – usage of ordered power display
Bit 13 – „1” – neutral wire current display
Bit 12 – „1” – mean active power display
Bit 11 – „1” – frequency display
Bit 10 – „1” – current THD display
Bit 9 – „1” – voltage THD display
Bit 8 – „1” – reactive inductive energy display
Bit 7 – „1” – reactive capacitive energy display
Bit 6 – „1” – active exported energy display
Bit 5 – „1” – active imported energy display
Bit 4 – „1” – power tangent display
Bit 3 – „1” – power factor display
Bit 2 – „1” – apparent power display
Bit 1 – „1” – reactive power display
Bit 0 – „1” – phase-to-phase volage display