6.5.1 Setting of Meter Parameters
In options menu choose
PAr
(using
or
buttons) and confirm selection with the
button.
item
parameter
name
m
arking
r
ange
n
otes/
description
m
anufacturer’s
value
1
Access
code entry
SeC
off,
1 … 60000
0 – no code
0
2
Current
transformer
ratio
tr_I
1 … 10000
1
3
Voltage
transformer
ratio
tr_u
0.1 … 4000.0
1
4
Mean ac-
tive power
synchroni-
zation
Syn
15, c_15,
c_30, c_60
Mean active power synchro-
nization:
15 - 15-minute moving
window
c_15 – measurement synchr.
with clock every 15 min.
c_30 – measurement synchr.
with clock every 30 min.
c_60 – measurement synchr.
with clock every 60 min.
15
5
Recording
minimal
and maxi-
mal values
complete
with errors
erLi
off, on
off – recording only correct
values (within measurement
range),
on – recording all errors
occurring in measurements
(values in 1e20 and -1e20
registers)
on
Table 3