37
4054
R
0..65535
Serial number two younger bytes
-
4055
R
0..65535
Software version (*100)
-
4056
RW
0..65535
quantity parameters displayed
0xffff
4057
Reserved
Brackets [ ] contain, respectively: resolution or unit.
energy is made available in hundreds of watt-hours (var-hours)
in double 16-bit register, and for this reason, one must divide
them by 10 when calculating values of particular energy from
registers, e.g.:
Imported active energy = (reg. value 4038 x 65536 +
reg. value 4039) / 10 [kWh]
exported active energy = (reg. value 4040 x 65536 +
reg. value 4041) / 10 [kWh]
exported inductive energy = (reg. value 4042 x 65536 +
reg. value 4043) / 10 [kVarh]
exported capacity energy = (reg. value 4044 x 65536
+ reg. value 4045) / 10 [kVarh]