35
4015
RW
0.1...35
quantity on the relay output of
alarm 1 (code as in Table 6)
24
4016
RW
0..5
Output type 1: 0 – n-on, 1– n-off,
2 – on, 3 – off, 4 – H-on,
5 – H-off
0
4017
RW
-1440...0...1440
[
o
/
oo
]
Lower value of the alarm 1 switch
of the rated input range
990
4018
RW
-1440...0...1440
[
o
/
oo
]
upper value of the alarm 1 switch
of the rated input range
1010
4019
RW
0...900 s
Alarm 1 switch delay value
(for AL_n = P_ord – register 4015
= 35, delay occurs only at alarm
activation)
0
4020
RW
0.1
Alarm 1 signalization latch
0
4021
RW
0...900 s
Alarm 1 re-activation block
0
4022
RW
0.1..35
quantity on the relay output of
alarm 2 (code as in Table 6)
24
4023
RW
0..5
Output type 1: 0 – n-on, 1– n-
off, 2 – on, 3 – off, 4 – H-on,
5 – H-off
0
4024
RW
-1440...0...1440
[
o
/
oo
]
Lower value of the alarm 2
switch of the rated input range
990
4025
RW
-1440...0...1440
[
o
/
oo
]
upper value of the alarm 2 switch
of the rated input range
1010
4026
RW
0...900 s
Alarm 2 switch delay value (for AL_n
= P_ord – register 4015 = 35, delay
occurs only at alarm activation)
0
4027
RW
0.1
Alarm 2 signalization latch
0
4028
RW
0...900 s
Alarm 2 re-activation block
0
4029
RW
5000 … 20000
No. of impulses for the impulse
output
5000
4030
RW
1..247
MODBuS Network Address
1
4031
RW
0..3
Transmission mode: 0->8n2,
1->8e1, 2->8o1, 3->8n1
0
Summary of Contents for PCE-ND10
Page 7: ...9 5 3 Connection diagrams OUT Direct measurement in a 4 wire network PCE ND10...
Page 8: ...10 OUTimp Semi indirect measurement in a 4 wire network PCE ND10...
Page 15: ...17 6 4 Operating modes Fig 6 PCE ND10 meter operating modes...
Page 24: ...26 Fig 8 Alarm types x alarm no a b normal c off d on a n on b n oFF c On d OFF...