34
Regi-
ster
ad-
dress
Ope-
ra-
tions
Range
Description
De-
fault
4000
RW
0 … 60000
Protection - password
0
4001
RW
Reserved
4002
RW
0...1200 [
o
/
oo
]
Mean ordered power *10
nominal signals
1000
4003
RW
1 … 10000
Current transformer ratio
1
4004
RW
1 … 40000
Voltage transformer ratio *10
10
4005
RW
0...3
Mean active power synchronization:
0 - 15-minute moving window
1 – measurement synchr. with
clock every 15 minutes,
2 – measurement synchr. with
clock every 30 minutes,
3 – measurement synchr. with
clock every 60 minutes
0
4006
RW
Reserved
4007
RW
0.1
Max and min value saving
method: 0 – no errors,
1 – with errors
0
4008
RW
Reserved
4009
RW
0.1
Reactive energy calculation
method:
0 – inductive and capacity energy
1 – positive and negative energy
0
4010
RW
0 … 61
Display panel illumination:
0 – off,
1-60 – illumination time in sec-
onds from pressing the button;
61 – always on
61
4011
RW
0..3
energy counters erasing
0 – no changes,
1 – erase active energies,
2 – erase reactive energies,
3 – erase all energies
0
4012
RW
0.1
erasing of mean active power P
AV
0
4013
RW
Reserved
4014
RW
0.1
erasing of min. and max.
0
Table 9
Summary of Contents for PCE-ND10
Page 7: ...9 5 3 Connection diagrams OUT Direct measurement in a 4 wire network PCE ND10...
Page 8: ...10 OUTimp Semi indirect measurement in a 4 wire network PCE ND10...
Page 15: ...17 6 4 Operating modes Fig 6 PCE ND10 meter operating modes...
Page 24: ...26 Fig 8 Alarm types x alarm no a b normal c off d on a n on b n oFF c On d OFF...