background image

24

Verify dust collector system airflow is adjusted to design 
conditions with a new, clean filter using the volume  
control dampers installed in the system. Failure to prop-
erly adjust system airflow will affect cartridge filter life.

The air volume should be adjusted based on the performance 
of the entire system. The air volume control damper must be 
adjusted to the system design airflow. Closing the volume 
control damper decreases system airflow. Opening the volume 
control damper increases system airflow.
Turn on the compressed air supply to the dust collector air 
manifold reservoir. Adjust the pressure regulator until the 
gauge reads 90-110 PSIG (6.2-7.6 BAR).

4.2  Checklist

Check the discharge of the blower assembly. Initially, 

some 

dust may discharge from the blower assembly as the filters are 
being seasoned. This may last several minutes after which the 
discharge air should remain visibly clean.
Measure the total airflow and static pressure at the inlet to the 
SFC unit. Adjust the blower damper for the desired airflow. 
Check to ensure that adequate air is being drawn into each 
of the collection points of the system. Adjust the individual 
dampers for each operation to balance the system airflow. 
Recheck the total system airflow and adjust the blower damper 
to desired system airflow. This procedure may need to be 
repeated several times until the entire system is within system 
design airflow specifications.
Check the differential pressure reading across the dust collector 
clean-to-dirty air sections. A normal differential pressure drop 
reading is between 1”-5” w.g. (25-127 mmAq). At start-up, 
this reading is generally in the 1”-3” w.g. (25-76 mmAq) range. 
Please list the reading here for future reference.
Initial dust collector differential pressure reading across filters is 
 __________” w.g. or __________ (mmAq) on __________ (date).

4.3   Checking the Pulse Cleaning System

Confirm the type of pulse cleaning controller delivered with your 
system. Your system was delivered with one of the following:
•    DPM Pulse Control Panel
•    DPC Pulse Monitor Panel
Check the pulse cleaning system for proper operation. The 
compressed air pressure should be between 90-110 PSIG 
(6.2-7.6 BAR). Parker’s pulse control panels are factory set to 
pulse every 10 seconds. Refer to the DPM/DPC Installation 
and Operation Manual specified with the dust collector to 
change these initial settings. Check to ensure the pulse 
(diaphragm) valves are “firing” at approximately 10-second 
intervals and deliver a crisp sounding pulse to each filter. 

 

The valves should not deliver a weak sound. If an extended 
“hiss” is heard afterwards, the pulse is too long, which does not 
assist in cleaning, and wastes compressed air.
•     If your system is supplied with a DPM Pulse Monitor Panel, 

place the “Continuous Clean/PS” switch on the timerboard 
to the “Continuous Clean” position. Or if the system is sup-
plied with DPC Pulse Control, place the “Continuous Clean/
PS” switch on the timerboard to PS position. The MOT AUX 
terminals at the timerboard should be field wired for the 
pulsing to become active. To activate, energize the motor 
starter to close the isolated auxiliary contact wired to the 
timerboard MOT AUX terminals. Verify consistent firing of 
each solenoid valve exhaust port.

NOTE:   It is important that the compressed air pressure is in the 

90-110 PSIG range (6.2-7.6 BAR) immediately prior to 
pulse. If the delivery capability of your compressed air 
source cannot return the manifold pressure to above 90 
PSIG during the “Pulse Delay” (factory set at 10 sec.) inter-
val, adjust the pulse delay at the timerboard and monitor 
the pressure. A longer interval will raise the operating pres-
sure, which is the pulse delay. (Adjust from position 2 to 
position 3 on the timer board.) Allow sufficient time for the 
system to stabilize after each adjustment before making 
any further adjustment. Adjust until the desired manifold 
pressure is reached.

4.3.1   Digital Pulse Monitor (DPM) Panel

The DPM is always set to “Continuous Clean” pulse mode, which 
means pulse cleaning is operating continuously when the system 
is online. Refer to the DPM/DPC Installation and Operation Manual 
for additional information.

4.3.2   Digital Pulse Control (DPC) Panel

The DPC Pulse Control Panel is set for “Pressure Switch” or “PS” 
pulse mode. With the DPC control, the desired pressure can be 
maintained by adjusting the high and low set-points on the panel. 
The factory setting is 3.0 (high set-point) and 2.5 (low set-point). 
This allows a 0.5” “deadband” and the pulse system will maintain 
the desired pressure. The high and low set-points on the DPC can 
be adjusted as the filters season and continuous pulsing occurs. 
Adjust upward in 0.5” increments until pulsing stops. Continue 
adjustments, when required, until the high set-point reaches 5”.  
No further adjustments should be made over 5” w.g.

5.  Service

Before servicing dust collector:
 • Wear appropriate protective clothing when servic-

ing dust collector.

 •Disconnect and lockout electrical power to the unit 

and control panel.

 •Close off and slowly bleed the compressed air  

supply from the air manifold reservoir. Air manifold 
reservoir pressure should be reduced to 0 PSIG (0 
BAR).

 •Collected dust may be hazardous. Consult proper 

authorities for handling and disposal.

 • Collected dust may be a potential fire hazard. 

Welding, grinding or operations involving open 
flames should not be performed without fire pro-
tection measures in place. Refer to Section 1 of 
this manual for additional precautions.

 • Disposal of collected dust must be according to 

federal, state and local regulations and all appropri-
ate authorities.

5.1  Cartridge Filter Removal and Replacement

ProTura

®

 Nanofiber filters are the only replacement filters which pro-

vide the highest level of performance expected from the SFC Dust 
Collector.

   CAUTION

 

!

  D A N G E R

Summary of Contents for SFC

Page 1: ...Downward Flow Cartridge Dust Collector Owner s Manual Model SFC...

Page 2: ...Parker Parker Order _________________________________________________________________ Unit Model ___________________________________________________________________ Unit Serial ______________________...

Page 3: ...odule Sections applies to 4 or more modules 6 3 4 Electrical Installation 11 3 4 1 Mounting the Controls 11 3 4 2 Solenoid Valve Enclosure Wiring 11 3 4 3 Heater Wiring 15 3 5 Compressed Air Connectio...

Page 4: ...Dust Removal 24 5 3 Servicing the Compressed Air Components 24 5 4 Servicing the Direct Drive Blower and Motor System 24 5 5 Servicing Cartridge Media 25 5 6 Servicing Optional Return Air Safety Filt...

Page 5: ...t collector The unit should be inspected frequently and dirt removed to prevent excessive accumulation which may result in flash over or fire damage The SFC system should not be used to support person...

Page 6: ...nt should be by a licensed contractor that is also experienced in potential fire and explosion hazards and adheres to related local state and federal codes standards laws and regulations Parker is not...

Page 7: ...v Page intentionally left blank...

Page 8: ...ding in non traffic areas even though the dust collector is equipped with an explosion vent 2 Introduction Thank you for selecting Parker dust collection equipment to assist you in your commitment to...

Page 9: ...nism provides brief bursts of compressed air directed through the diaphragm valves toward the cartridge filter This pulsing action dislodges the collected particles from the media where they fall into...

Page 10: ...crating strapping and hold down bolts Locate all hardware bags sealant and other assembly materials provided with your unit 3 Installation 3 1 Off Loading and Inspection SFC dust collector modules are...

Page 11: ...4 FIGURE 2 SFC Typical SINGLE UNIT Installation Diagram PARKER PARKER 44 10335 0001...

Page 12: ...5 FIGURE 3 Recommended Unit Clearances 44 10337 0001...

Page 13: ...hopper and filter module together Securely tighten all hardware at the filter module and hopper Recheck leg assembly sway braces to ensure they are tight Install fasteners bolt flat washer lock washer...

Page 14: ...7 FIGURE 4 Single Hopper SFC 44 10309 0001...

Page 15: ...8 FIGURE 5 Multiple Hopper SFC 44 10309 0002...

Page 16: ...9 FIGURE 6 Multiple Hopper SFC 44 10309 0003...

Page 17: ...10 FIGURE 7 Multiple Modules SFC 44 10310 0001...

Page 18: ...pulse cleaning Motor starter with Digital Pulse Control DPC for on demand pulse cleaning VFD with DPM for continuous pulse cleaning VFD with DPC for on demand pulse cleaning Refer to Parker sales orde...

Page 19: ...12 FIGURE 8 SFC Pressure Gauge Installation 44 10333 0001 Rev A...

Page 20: ...13 FIGURE 9 Solenoid Wiring to Pulse Controls for 2 3 4 and 5 Tier Units...

Page 21: ...14 FIGURE 10 Pneumatic Valve Assembly 44 10332 0001...

Page 22: ...l compressed air supply pipe fittings and connections 3 6 Assembly of Optional Equipment 3 6 1 Blower Purge Package Installation TIP OVER HAZARD Anchor dust collector to concrete pad prior to install...

Page 23: ...16 FIGURE 11 Legs Support Top Mount Blower 44 10331 0001 NOTE FOR BLOWERS 20 HP OR LARGER SUPPORT LEGS ARE REQUIRED TO BE INSTALLED UNDER THE CLEAN AIR PLENUM...

Page 24: ...17 FIGURE 12 Abrasive Inlet Installation 44 10338 0001...

Page 25: ...ry air lock Do not allow any object to be placed in or near the rotary air lock during operation Verify rotary air lock rotation matches rotation arrows affixed to assembly 3 6 4 Abrasive Inlet Instal...

Page 26: ...s not designed for dust storage The slide gate should remain open during normal operation 3 6 6 Inlet Cover and Blank Cover Plate Installation Inlet collar and blank cover plates bolt directly to the...

Page 27: ...20 FIGURE 16 EDAP Interconnection FIGURE 15 EDAP Installation 48 10007...

Page 28: ...transport an assembled 5 high unit due to height restrictions within the vehicle When shipping this unit it will be necessary to ship the EDAP separately This will require the customer to assemble th...

Page 29: ...interchange at motor junction box Engage starter disconnect switch start blower and recheck rotation NOTE Proper blower rotation is required to move the designed amount of air A blower rotating in the...

Page 30: ...23 FIGURE 17 SFC Series Door Filter Installation 44 10329 0001...

Page 31: ...timerboard to the Continuous Clean position Or if the system is sup plied with DPC Pulse Control place the Continuous Clean PS switch on the timerboard to PS position The MOT AUX terminals at the time...

Page 32: ...ace prior to being closed A flat solid section of door handle will be visible when door assembly is in the properly closed position Refer to Figure 17 If cam surface of the door handle is visible Quic...

Page 33: ...for HEPA filters TABLE 2 Cartridge Filters CARTRIDGE FILTER PARKER PART NUMBER GENERAL DESCRIPTION OF FILTER MEDIA ProTura Nanofiber 33 10089 ProTura Nanofiber layer on cellulose ProTura Nanofiber FR...

Page 34: ...l This may require bending panel sections away from the frame for frame removal Care should be taken to avoid sharp panel edges during this activity 4 Dispose of the removed rupture panel in accordanc...

Page 35: ...proper motor starter overload rating against full load amps on motor name plate Adjust or replace overloads as required Ensure drum is properly sealed against drum lid package Ensure drum lid package...

Page 36: ...ge to the timer board and voltage output from timer boards to solenoid valves Consult DPM DPC Pulse Control Panel Installation and Operation Manual for additional assistance Reduce high set point on D...

Page 37: ...30 7 Illustrated Parts FIGURE 21 SFC Series 44 10330 0001 FIGURE 22 SFC Series Explosion Vents...

Page 38: ...0020 20 Gallon Drum Lid 9 45 10022 0055 55 Gallon Quick Release Collar 9A 45 10022 0020 20 Gallon Drum Quick Release Collar 10 15 0233 14 Hose Clamp 11 15 0202 14 Flexible Duct 12 18 0944 14 Adapter...

Page 39: ...32 Page intentionally left blank...

Page 40: ...or misuse misapplication or normal wear and tear e Equipment not properly installed operated and maintained under normal conditions and recommended applications As Buyers exclusive remedy for any def...

Page 41: ...shooting effort details 5 Description of physical location and or environment details The Buyer shall cooperate with PARKER in its investigation and provide full information and documentation concerni...

Page 42: ...arker com dhfns Hiross Zander Essen Germany 49 2054 9340 www parker com hzfd Padova Italy 39 049 9712 111 www parker com hzfd Engine Filtration Water Purification Racor Dewsbury England 44 0 1924 487...

Reviews: