background image

11

Disconnect lifting slings and spreader bars used for installation.

Apply sealant to the next hoppers that will receive a filter module 
(refer to Figure 7). Apply sealant to the side bolting flange of 
the next filter module to be installed using the “figure 8” pattern 
(refer to Figure 7, Detail B). Place this module on its hopper. Use 
the hardware provided (refer to Figure 7, Detail B).

Place this module on its hopper. Use the hardware provided 
(refer to Figure 7, Detail B) and bolt the module sections 
together. Bolt the filter module to the hopper (refer to Figure 7, 
Detail A). Securely tighten all hardware at the filter module and 
hopper. Recheck leg assembly sway braces to ensure they are 
tight. Install fasteners (bolt, flat washer, lock-washer, nut) to all 
four pry locations.

Disconnect lifting slings and spreader bars used for installation.

Repeat this process until all the module sections are in place, 
securely fastened and anchored to the foundation. Recheck all 
hardware connections to make certain they are securely tight-
ened. Remove lift slings and spreader bars and clear all tools 
from the work area.

NOTE:   Make certain all bolts (including the anchor bolts) are 

properly tightened before proceeding with the remain-
der of the installation.

Install all cartridge filters removed at the beginning of the instal-
lation process and install the filter access doors (refer to Section 
5.1).

3.4  Electrical Installation

ELECTRICAL SHOCK HAZARD

All electrical work should be performed by a qual- 
ified electrician in accordance with local electrical 
codes. Disconnect electrical power before install-
ing or servicing any electrical component.

General

Several types of standard electrical components can be 
installed to control and monitor your dust collector. A VFD or 
a motor starter circuit (combination starter panel) is required to 
safely start and stop the system. A properly sized circuit breaker 
or fused disconnect is also required to safely work on and 
service the electrical system. In addition, a 115/1/60 (2 amp) 
control circuit is required for the pulse control panel. Some or 
all of the above items may be included in the controls package 
you purchased from Parker. Any one of the following control 
combinations can be used:
•  Motor starter with Digital Pulse Monitor (DPM) for continuous 

pulse cleaning.

•  Motor starter with Digital Pulse Control (DPC) for on-demand 

pulse cleaning.

• VFD with DPM for continuous pulse cleaning.
• VFD with DPC for on-demand pulse cleaning.
Refer to Parker sales order to verify the control configuration 
purchased with your unit and whether additional items are 
required to control and operate your system.

3.4.1 Mounting The Controls

Mount the VFD or combination starter panel for the fan motor 
in a convenient location. It is recommended that these controls 
be mounted on a wall or pedestal in an area subject to minimal 
vibration and electrical noise. Mounting hardware is provided by 
the customer or the contractor. If the panel includes the DPM or 
the DPC gauge and Parker timer control board, then the location 
of the panel must within close proximity of the dust collection 
unit as shown in Figure 8. For additional setup and installation  
information refer to the VFD and/or DPM/DPC Owner’s Manuals 
provided.

 Avoid mounting the panel on the collector due to 
vibration generated from blower assembly and the 
pulsing system.

 

For all pulse control panels, connect the black plastic pressure 
tubing (25’ [7.5 meters] provided by Parker) to the panel fittings 
and the SFC unit. Connect the dirty air plenum of the SFC to 
the high pressure port (dirty air) on the panel as shown in Figure 
8. Connect the clean air plenum of the SFC to the low pressure 
port (clean air) on the panel. 

3.4.2   Solenoid Valve Enclosure Wiring

The solenoid valves at the dust collector must be wired cor-
rectly to the pulse control panel. Refer to Figure 9 when making 
connections from the pulse control panel to the solenoid valve 
enclosure(s).

Example: Figure 9 shows the SFC having ten valve locations 
per module. This means when the system pulses, “1” is the first 
pulse in the sequence, “2” is the second, “3” is the third, etc.

When multiple dust collector modules are installed, 

 

daisy chain the wiring so that each solenoid valve with the 
same module location will pulse at the same time. This means 
all #1 solenoid valves are connected together and wired to 
pulse control panel “OUT 1,” #2 solenoid valves are connected 
together and wired to pulse control panel “OUT 2,” etc. Refer 
to Figure 9 for the SFC dust collector solenoid valve wiring 
information. When cleaning, the pulse valves sequence left to 
right, top to bottom.

Unless specified on the Parkerr sales order, the customer will 
supply interconnecting material (conduit, wiring, etc.) from the 
pulse control panel to the SFC

.

   CAUTION

 

!

  D A N G E R

Summary of Contents for SFC

Page 1: ...Downward Flow Cartridge Dust Collector Owner s Manual Model SFC...

Page 2: ...Parker Parker Order _________________________________________________________________ Unit Model ___________________________________________________________________ Unit Serial ______________________...

Page 3: ...odule Sections applies to 4 or more modules 6 3 4 Electrical Installation 11 3 4 1 Mounting the Controls 11 3 4 2 Solenoid Valve Enclosure Wiring 11 3 4 3 Heater Wiring 15 3 5 Compressed Air Connectio...

Page 4: ...Dust Removal 24 5 3 Servicing the Compressed Air Components 24 5 4 Servicing the Direct Drive Blower and Motor System 24 5 5 Servicing Cartridge Media 25 5 6 Servicing Optional Return Air Safety Filt...

Page 5: ...t collector The unit should be inspected frequently and dirt removed to prevent excessive accumulation which may result in flash over or fire damage The SFC system should not be used to support person...

Page 6: ...nt should be by a licensed contractor that is also experienced in potential fire and explosion hazards and adheres to related local state and federal codes standards laws and regulations Parker is not...

Page 7: ...v Page intentionally left blank...

Page 8: ...ding in non traffic areas even though the dust collector is equipped with an explosion vent 2 Introduction Thank you for selecting Parker dust collection equipment to assist you in your commitment to...

Page 9: ...nism provides brief bursts of compressed air directed through the diaphragm valves toward the cartridge filter This pulsing action dislodges the collected particles from the media where they fall into...

Page 10: ...crating strapping and hold down bolts Locate all hardware bags sealant and other assembly materials provided with your unit 3 Installation 3 1 Off Loading and Inspection SFC dust collector modules are...

Page 11: ...4 FIGURE 2 SFC Typical SINGLE UNIT Installation Diagram PARKER PARKER 44 10335 0001...

Page 12: ...5 FIGURE 3 Recommended Unit Clearances 44 10337 0001...

Page 13: ...hopper and filter module together Securely tighten all hardware at the filter module and hopper Recheck leg assembly sway braces to ensure they are tight Install fasteners bolt flat washer lock washer...

Page 14: ...7 FIGURE 4 Single Hopper SFC 44 10309 0001...

Page 15: ...8 FIGURE 5 Multiple Hopper SFC 44 10309 0002...

Page 16: ...9 FIGURE 6 Multiple Hopper SFC 44 10309 0003...

Page 17: ...10 FIGURE 7 Multiple Modules SFC 44 10310 0001...

Page 18: ...pulse cleaning Motor starter with Digital Pulse Control DPC for on demand pulse cleaning VFD with DPM for continuous pulse cleaning VFD with DPC for on demand pulse cleaning Refer to Parker sales orde...

Page 19: ...12 FIGURE 8 SFC Pressure Gauge Installation 44 10333 0001 Rev A...

Page 20: ...13 FIGURE 9 Solenoid Wiring to Pulse Controls for 2 3 4 and 5 Tier Units...

Page 21: ...14 FIGURE 10 Pneumatic Valve Assembly 44 10332 0001...

Page 22: ...l compressed air supply pipe fittings and connections 3 6 Assembly of Optional Equipment 3 6 1 Blower Purge Package Installation TIP OVER HAZARD Anchor dust collector to concrete pad prior to install...

Page 23: ...16 FIGURE 11 Legs Support Top Mount Blower 44 10331 0001 NOTE FOR BLOWERS 20 HP OR LARGER SUPPORT LEGS ARE REQUIRED TO BE INSTALLED UNDER THE CLEAN AIR PLENUM...

Page 24: ...17 FIGURE 12 Abrasive Inlet Installation 44 10338 0001...

Page 25: ...ry air lock Do not allow any object to be placed in or near the rotary air lock during operation Verify rotary air lock rotation matches rotation arrows affixed to assembly 3 6 4 Abrasive Inlet Instal...

Page 26: ...s not designed for dust storage The slide gate should remain open during normal operation 3 6 6 Inlet Cover and Blank Cover Plate Installation Inlet collar and blank cover plates bolt directly to the...

Page 27: ...20 FIGURE 16 EDAP Interconnection FIGURE 15 EDAP Installation 48 10007...

Page 28: ...transport an assembled 5 high unit due to height restrictions within the vehicle When shipping this unit it will be necessary to ship the EDAP separately This will require the customer to assemble th...

Page 29: ...interchange at motor junction box Engage starter disconnect switch start blower and recheck rotation NOTE Proper blower rotation is required to move the designed amount of air A blower rotating in the...

Page 30: ...23 FIGURE 17 SFC Series Door Filter Installation 44 10329 0001...

Page 31: ...timerboard to the Continuous Clean position Or if the system is sup plied with DPC Pulse Control place the Continuous Clean PS switch on the timerboard to PS position The MOT AUX terminals at the time...

Page 32: ...ace prior to being closed A flat solid section of door handle will be visible when door assembly is in the properly closed position Refer to Figure 17 If cam surface of the door handle is visible Quic...

Page 33: ...for HEPA filters TABLE 2 Cartridge Filters CARTRIDGE FILTER PARKER PART NUMBER GENERAL DESCRIPTION OF FILTER MEDIA ProTura Nanofiber 33 10089 ProTura Nanofiber layer on cellulose ProTura Nanofiber FR...

Page 34: ...l This may require bending panel sections away from the frame for frame removal Care should be taken to avoid sharp panel edges during this activity 4 Dispose of the removed rupture panel in accordanc...

Page 35: ...proper motor starter overload rating against full load amps on motor name plate Adjust or replace overloads as required Ensure drum is properly sealed against drum lid package Ensure drum lid package...

Page 36: ...ge to the timer board and voltage output from timer boards to solenoid valves Consult DPM DPC Pulse Control Panel Installation and Operation Manual for additional assistance Reduce high set point on D...

Page 37: ...30 7 Illustrated Parts FIGURE 21 SFC Series 44 10330 0001 FIGURE 22 SFC Series Explosion Vents...

Page 38: ...0020 20 Gallon Drum Lid 9 45 10022 0055 55 Gallon Quick Release Collar 9A 45 10022 0020 20 Gallon Drum Quick Release Collar 10 15 0233 14 Hose Clamp 11 15 0202 14 Flexible Duct 12 18 0944 14 Adapter...

Page 39: ...32 Page intentionally left blank...

Page 40: ...or misuse misapplication or normal wear and tear e Equipment not properly installed operated and maintained under normal conditions and recommended applications As Buyers exclusive remedy for any def...

Page 41: ...shooting effort details 5 Description of physical location and or environment details The Buyer shall cooperate with PARKER in its investigation and provide full information and documentation concerni...

Page 42: ...arker com dhfns Hiross Zander Essen Germany 49 2054 9340 www parker com hzfd Padova Italy 39 049 9712 111 www parker com hzfd Engine Filtration Water Purification Racor Dewsbury England 44 0 1924 487...

Reviews: