Gem6K Hardware Installation Guide
GPDM Specifications
Activation Conditions:
Turn on: 398VDC
Turn off: 380VDC
Resistance:
Six 100 ohm resistors in parallel (16.7 ohm equivalent)
Continuous Dissipation:
300W in 25
°
C internal ambient
Maximum Dissipation:
9KW
Maximum Pulse Energy:
13KJ (pulse rating of resistors, repeatable, not to
exceed continuous rating)
Weight:
3.1 pounds (1.4 kg)
GPDM LED Color Code:
Left:
Right:
Status:
Green
Off
ready
Green
Yellow*
active
Red
Off
fault (max. temperature, duty cycle, or pulse exceeded)
*Yellow LED may flash or be continuously illuminated until GPDM stops dissipating
GPDM Connection Instructions
WARNING
Sheet metal and exhaust air at the top of the enclosure are hot. Avoid contact.
WARNING
V BUS+ and V BUS- terminals are at hazardous voltages when power is applied,
and for up to 30 seconds after power is removed. Lower voltages may still be
present for several minutes after power is removed. Reinstall the clear plastic
terminal cover after you make connections.
WARNING
Only connect V BUS
±
terminals of drives that share the same fused AC power
source, as shown in the next drawing.
Connecting the GPDM
1.
Connect up to three GV, GV6 or GV6K Servo Drives to one GPDM. (Connect
only
GV(6)(K)-U3n/U6n/U12n drives; do not connect any other drives to the GPDM.)
2.
Connect drive V BUS+ terminals to V BUS+ on the GPDM.
3.
Connect drive V BUS– terminals to V BUS– on the GPDM.
4.
For multiple drives, connect drive safety earth terminals to a single point ground.
5.
Keep connections between drive and GPDM less than 12 inches (300 mm). Use 14
AWG (2.5 mm
2
) or greater diameter wire.