Drive Controlled Pump
Parker Hannifin Corporation
Hydraulics Group
DCP Manual innen A4 UK.indd 06.11.17
63
Manual
Electrical Ratings (400 V build variant), Frame K
Power Supply = 380-480 V ±10 %, 50/60 Hz ±5 %
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Minimum repetitive power up / power down cycle time = 10 min
Product Code
Motor Power
Output Current
(A)
Input Current (A)
Estimated
Efficiency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate
%/kHz
Frame K:
Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short
circuit current 18 kA.
Normal Duty (Output Overload Motoring 110% for 60s)
DCP315
160kW
250Hp
315
302
276
279
98 %
2 / 08
8,5 %
DCP380
200kW
300Hp
380
361
343
333
98 %
2 / 08
7,7 %
DCP440
250kW
350Hp
440
414
428
389
98 %
2 / 08
8,3 %
Heavy Duty (Output Overload Motoring 150 % for 60 s, 18 0% for 3 s short term rating)
DCP315
132kW
200Hp
260
240
229
225
98 %
2 / 08
7,7 %
DCP380
160kW
250Hp
315
302
276
279
98 %
2 / 08
6,9 %
DCP440
200kW
300Hp
380
361
344
334
98 %
2 / 08
7,5 %
Input fuse ratings (A) Europe 400V model
Order code
Normal duty
Heavy duty
Frame size
DCP33P5
6A
6A
D
DCP34P5
8A
6A
D
DCP35P5
10A
8A
D
DCP37P5
10A
8A
D
DCP3010
12A
10A
D
DCP3012
16A
10A
D
DCP3016
20A
16A
E
DCP3023
25A
20A
E
DCP3032
32A
25A
F
DCP3038
40A
32A
F
DCP3045
63A
50A
G
DCP3060
80A
70A
G
DCP3073
100A
90A
G
DCP3087
125A
125A
H
DCP3105
150A
150A
H
DCP3145
200A
200A
H
DCP3180
250A
250A
J
DCP3205
315A
315A
J
DCP3260
400A
400A
J
DCP3315
400A
400A
K
DCP3380
500A
500A
K
DCP3440
630A
630A
K