Drive Controlled Pump
Parker Hannifin Corporation
Hydraulics Group
DCP Manual innen A4 UK.indd 06.11.17
60
Manual
The forced-vent cooling of the drive is achieved by 1, or in some cases 2 fans. The Fan Rating gives the volume of air venting from the drive.
Electrical Ratings (400 V build variant), Frame D
Product
Fan Ratings
FRAME D
All models
1 off 27 cfm (45m³/hr)
FRAME E
All models
1 off 33 cfm (56m³/hr)
FRAME F
All models
2 off 27 cfm (45m³/hr)
FRAME G
All models
2 off 53 cfm (89 m³/hr)
FRAME H
45kW
55 – 75kW
2 off 27 cfm (45 m³/hr)
2 off 53 cfm (89 m³/hr)
FRAME J
All Models
2 off 27 cfm (45 m³/hr)
3 off 80 cfm (133 m³/hr)
FRAME K
All Models
1 off 518 cfm (880 m³/hr)
Power Supply = 380-480V ±10 %, 50/60 Hz ±5%
Motor power. output current and input current must not be exceeded under steady state operating conditions
Minimum repetitive power up / power down cycle time = 10 mins
Product Code
Motor Power
Output Current
(A)
Input Current
(A)
Estimated Effici-
ency
Switching Frequency
(kHz)
nominal / maximum
Output Current Derate
%/kHz
(applied above nominal
switching frequency)
Frame D: Input currents for kW ratings are at 400V 50Hz ac input and for Hp ratings at 460V 60Hz ac input. Prospective short circuit
current 5kA.
Normal Duty (Output Overload Motoring 110% for 60s)
DCP33P5
1.1 kW
3.5
4.0
95 %
4 / 16
2.4 %
1.5 PS
3.0
3.5
DCP34P5
1.5 kW
4.5
5.3
96 %
4 / 16
3.7 %
2 PS
3.4
4.5
DCP35P5
2.2 kW
5.5
7.6
97 %
4 / 16
4.5 %
3 PS
4.8
6.4
DCP37P5
3 kW
7.5
6.5
97 %
4 / 16
4.0 %
4 kW
10.0
8.0
DCP3010
4 kW
10.0
8.0
97 %
4 / 16
3.9 %
5 PS
7.6
6.6
DCP3012
5.5 kW
12.0
10.6
97 %
4 / 16
3.5 %
7.5 PS
11.0
9.4
Heavy Duty (Output Overload Motoring 150% for 60s, 180% for 0.3s short term rating)
DCP33P5
0.75 kW
2.5
2.9
95 %
4 / 16
1.0 %
1 PS
2.1
2.4
DCP34P5
1.1 kW
3.5
4.0
95 %
4 / 16
3.1 %
1.5 PS
3.0
3.5
DCP35P5
1.5 kW
4.5
5.3
96 %
4 / 16
4.3 %
2 PS
3.4
4.5
DCP37P5
2.2 kW
5.5
5.2
97 %
4 / 16
3.8 %
3 PS
4.8
4.6
DCP3010
3 kW
7.5
6.5
97 %
4 / 16
3.8 %
DCP3012
4 kW
10.0
8.0
97 %
4 / 16
3.3 %
5 PS
7.6
6.6
Internal cooling fans