background image

6   

Programming Guide

ZONE PROGRAMMING

When programming zones please note that the Spectra control panels’ zone assignment is dependent on where
the detection devices in the system are connected (see Table 2 below).
 

 

WHAT IS AN EXPANSION INPUT?

There are a total of eight expansion inputs available. Each hardwired input on a Zone Expansion Module or wireless
transmitter used by the Liberator

TM

 Wireless Bus Module can be assigned to an expansion input. The expansion inputs can

be used in any combination. For example, you can assign four wireless transmitters as well as 4 hardwire inputs to the
expansion inputs. Regardless of how many expansion modules are being used, 

the control panel cannot support more

than eight expansion inputs

. The expansion module inputs are assigned as follows:

SPC-319 Liberator Wireless Bus Module

Wireless transmitters assigned to sections 

[601]

 to 

[608]

 of the control panel represent expansion inputs 1 to 8 respectively.

Refer to 

Wireless Transmitter Assignment

 on page 22.

SPC-ZX4 and SPC-ZX8 Zone Expansion Module

Detection devices connected to input terminals Z1 to Z4 of the SPC-ZX4 module or Z1 to Z8 of the SPC-ZX8 module,
represent expansion inputs 1 to 8 respectively. Please note that the module’s inputs must be enabled in section 

[651]

 of the

control panel. Refer to 

Zone Assignment 

on page 25.

Do not assign devices from different modules to the same expansion input. For example, do not assign a
wireless transmitter to section [601], then connect a detection device to input Z1 of the SPC-ZX8 and enable
option [1] in section [651].

 

  

Table 2: Zone Recognition Table

Device connected to 

which input?

1725EX               1725
1755EX               1755

1728EX               1728
1758EX               1758

NO ATZ           WITH ATZ

NO ATZ           WITH ATZ

Control Panel Input 1 = 

Zone 1            Zone 1 & 4

Zone 1            Zone 1 & 6

Control Panel Input 2 =

Zone 2            Zone 2 & 5

Zone 2            Zone 2 & 7

Control Panel Input 3 =

Zone 3            Zone 3 & 6

Zone 3            Zone 3 & 8

Control Panel Input 4 =

N/A                 N/A

Zone 4            Zone 4 & 9

Control Panel Input 5 =

N/A                 N/A

Zone 5            Zone 5 & 10

Keypad Zone 1 = 

Zone 4            Zone 7

Zone 6            Zone 11

Keypad Zone 2 = 

Zone 5            Zone 8

Zone 7            Zone 12

Expansion Input 1 = 

Zone 6            Zone 9

Zone 8            Zone 13

Expansion Input 2 = 

Zone 7            Zone 10

Zone 9            Zone 14

Expansion Input 3 = 

Zone 8            Zone 11

Zone 10          Zone 15

Expansion Input 4 = 

Zone 9            Zone 12

Zone 11          Zone 16

Expansion Input 5 = 

Zone 10          Zone 13

Zone 12          N/A

Expansion Input 6 = 

Zone 11          Zone 14

Zone 13          N/A

Expansion Input 7 = 

Zone 12          Zone 15

Zone 14          N/A

Expansion Input 8 = 

Zone 13          Zone 16

Zone 15          N/A

Summary of Contents for Spectra 1725

Page 1: ...PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1 2 1725 1725EX 1728 AND 1728EX 1755 1755EX 1758 AND 1758EX...

Page 2: ......

Page 3: ...RT CODES 16 Arming Report Codes 16 Disarming Report Codes 16 Alarm Report Codes 17 Tamper Report Codes 17 System Trouble Report Codes 17 Programmable Ademco Contact ID Report Code List 18 All Codes Ad...

Page 4: ...ypass Recall Feature 33 One Touch Arming 33 Keyswitch Arming 33 Panic Alarms 33 Auto Arming 34 Alarm Memory Display 34 Programming Chime Zones 34 Keypad Muting 34 Quick Function Keys 34 HARDWARE CONNE...

Page 5: ...Spectra Series 3...

Page 6: ...ctions 001 to 016 127 to 138 302 to 348 610 650 to 651 After entering the programming mode as described in the shaded box above each option from 1 to 8 will represent a specific feature or option Pres...

Page 7: ...ote controls see page 28 Download to DESTINATION Control Panel 1 Remove AC and battery power from the control panel 2 Insert the Memory Key onto the serial connector labeled KEY on the Spectra control...

Page 8: ...odule or Z1 to Z8 of the SPC ZX8 module represent expansion inputs 1 to 8 respectively Please note that the module s inputs must be enabled in section 651 of the control panel Refer to Zone Assignment...

Page 9: ...____ ____ ____ 1 2 3 4 5 6 7 8 010 Zone 10 ____________________ ____ ____ 1 2 3 4 5 6 7 8 011 Zone 11 ____________________ ____ ____ 1 2 3 4 5 6 7 8 012 Zone 12 ____________________ ____ ____ 1 2 3 4...

Page 10: ...2 45 sec 071 ___ ___ ___ seconds EXIT DELAY 1 30 sec 072 ___ ___ ___ seconds EXIT DELAY 2 30 sec 073 ___ ___ ___ minutes 000 no bell on alarm BELL CUT OFF TIME PARTITION 1 4 min 074 ___ ___ ___ minute...

Page 11: ...6 Zones 1 to 16 99 Any Zone 02 Partition Status 00 System not ready Partition 1 only 01 System ready Partition 1 only 02 Steady Alarm in Partition 03 Pulsed Alarm in Partition 04 Pulsed or Steady Alar...

Page 12: ...to Close auto arming failed 02 No Movement Auto Arming 03 Partial Arming stay force instant bypass 04 One Touch Arming 05 Arm with WinLoad Software 06 Arm with Keyswitch 99 Any Sub Group 15 Disarm wi...

Page 13: ...re Partition 1 only 01 AC Loss restore Partition 1 only 02 Battery Failure restore Partition 1 only 03 Auxiliary current overload restore Partition 1 only 04 Bell current overload restore Partition 1...

Page 14: ...d 2 Tamper Supervision l Disabled l Enabled SECTION 129 General Options Option OFF ON 1 PGM2 Output Activation Option l Steady l Pulse flash 2 PGM2 Pulse Once Every 30sec If System Armed l Disabled l...

Page 15: ...s l No 8 Normal State of Global PGM l Normally Closed N C l Normally Open SECTION 132 Zone Options Option OFF ON 1 2 l see table l see table l see table l see table 3 Generate Tamper if detected on By...

Page 16: ...ure Use l N A l N A SECTION 136 Dialer Options Option OFF ON 1 Call Back l Disabled l Enabled 2 Automatic Event Buffer Transmission l Disabled l Enabled 3 Contact I D Report Codes l Programmable l All...

Page 17: ...__ __ __ __ __ __ __ __ CENTRAL STATION TELEPHONE OR PAGER NUMBER 1 32 DIGITS if less than 32 press ENTER to accept 152 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __...

Page 18: ...ode 37 __ __ Access code 38 __ __ Access code 39 __ __ Access code 40 170 __ __ Access code 41 __ __ Access code 42 __ __ Access code 43 __ __ Access code 44 171 __ __ Access code 45 __ __ Access code...

Page 19: ...12 200 __ __ Zone 13 __ __ Zone 14 __ __ Zone 15 __ __ Zone 16 RESTORE 201 __ __ Zone 1 __ __ Zone 2 __ __ Zone 3 __ __ Zone 4 202 __ __ Zone 5 __ __ Zone 6 __ __ Zone 7 __ __ Zone 8 203 __ __ Zone 9...

Page 20: ...m Peripheral 43 525 Reversing Relay Disable 70 134 Entry Exit 15 331 Polling Loop Open 44 SYSTEM PERIPHERAL DISABLES 530 540 135 Day Night 16 332 Polling Loop Short 45 COMMUNICATION DISABLES 550 560 1...

Page 21: ...n by user Disarm after alarm with Keyswitch 1 4A9 Keyswitch Open Auto Arming Cancellation 1 4A5 Deferred Open Close Disarm with PC software 1 4A7 Remote arm disarm Disarm after an alarm with PC softwa...

Page 22: ...Low Battery 3 384 RF xmtr low battery Wireless Transmitter Supervision Loss 3 381 Loss of super RF Module fault restore 3 333 Expansion module failure restore Printer fault restore 3 336 Local printe...

Page 23: ...ser Code 018 1 2 3 4 5 6 7 8 319 User Code 019 1 2 3 4 5 6 7 8 320 User Code 020 1 2 3 4 5 6 7 8 321 User Code 021 1 2 3 4 5 6 7 8 322 User Code 022 1 2 3 4 5 6 7 8 323 User Code 023 1 2 3 4 5 6 7 8 3...

Page 24: ..._EXPANSION INPUT 1 602 ___ ___ ___ ___ ___ ___EXPANSION INPUT 2 603 ___ ___ ___ ___ ___ ___EXPANSION INPUT 3 604 ___ ___ ___ ___ ___ ___EXPANSION INPUT 4 605 ___ ___ ___ ___ ___ ___EXPANSION INPUT 5 6...

Page 25: ...ts will appear one at a time by illuminating the corresponding light To view the next digit press the ENTER key On LCD keypads the entire serial number will appear on the screen STEP 4 Return to STEP...

Page 26: ...ng of 3 characters and up is acceptable Section Description 631 Display Signal Strength of Expansion Input 1 Section 601 632 Display Signal Strength of Expansion Input 2 Section 602 633 Display Signal...

Page 27: ...sion Module Tamper Recognition l Disabled l Z1 becomes tamper input 3 PGM1 on Zone Expansion Module follows Global PGM programmed in sections 124 125 l Disabled l Enabled 4 Future Use l N A l N A 5 Fu...

Page 28: ...vate 100mS after any of the above events have occurred if programmed RESET ZONE EXPANSION MODULE 660 PRESS ENTER TO CONFIRM WILL RESET THE ZONE MODULE S SECTIONS 650 TO 657 TO DEFAULT VALUES Event Gro...

Page 29: ...TE CONTROL 1 A B C D A B C D A C B D 712 ____ ____ ____ ____ ____ ____ ____ ____ REMOTE CONTROL 2 A B C D A B C D A C B D 713 ____ ____ ____ ____ ____ ____ ____ ____ REMOTE CONTROL 3 A B C D A B C D A...

Page 30: ...E CONTROL TWICE YOU WILL HEAR A CONFIRMATION BEEP REMOTE CONTROL 4 735 PRESS A BUTTON ON A REMOTE CONTROL TWICE YOU WILL HEAR A CONFIRMATION BEEP REMOTE CONTROL 5 736 PRESS A BUTTON ON A REMOTE CONTRO...

Page 31: ...Bell Current The BELL output uses a fuseless circuit and will automatically shut down if the current exceeds 3A with a 1725 1725EX 1728 or 1728EX or 2 5A with a 1755 1755EX 1758 or 1758EX After openin...

Page 32: ...ssigned to partition 1 Master Code 2 is permanently assigned to partition 2 except when partitioning is disabled Master Code 2 will be assigned to partition 1 and can be used to create modify or delet...

Page 33: ...d If you make a mistake the keypad will emit a REJECTION BEEP When you have correctly Stay Armed the system the appropriate ARM indication will appear and the Exit Delay will be initiated Stay Arming...

Page 34: ...emit a REJECTION BEEP When correctly Force Armed the appropriate ARM indication will appear and the Exit Delay will be initiated Please note that Force Arming can also be activated using One Touch Fo...

Page 35: ...ress and hold the ENTER button for 3 seconds The system will switch to Exit Delay mode At the end of the Exit Delay period the control panel will switch to Regular Arming To Exit and Force Arm Press a...

Page 36: ...on Enter the 2 digit 01 to 16 zone number s When the corresponding LED is on the zone is chimed When the corresponding LED is off the zone is unchimed When the desired zones are chimed press ENTER LCD...

Page 37: ...Spectra Series 35 HARDWARE CONNECTIONS SINGLE ZONE INPUTS DOUBLE ZONE INPUTS with ATZ option only...

Page 38: ...36 Programming Guide CONNECTING A KEYSWITCH CONNECTING FIRE CIRCUITS PGM CONNECTIONS...

Page 39: ...Spectra Series 37 CONNECTING A LIBERATOR WIRELESS BUS MODULE SPC 319 CONNECTING A ZONE EXPANSION MODULE SPC ZX8...

Page 40: ...38 Programming Guide SPECTRA 1725 1725EX 1728 AND 1728EX PCB LAYOUT...

Page 41: ...river Option Only An optional siren driver is available with the Spectra 1755 1755EX 1758 and 1758EX control panels This siren driver allows you to connect speakers directly to the bell output as show...

Page 42: ......

Reviews: