ZONE EXPANSION MODULES (SPC-ZX4/8)
The following options and features are only available to program when a
Zone Expansion Bus Module
has been
connected to the Spectra control panel’s communication bus as shown on page 37. The Zone Expansion Modules
provide you with up to 4 (SPC-ZX4) or up to eight (SPC-ZX8) additional hardwired inputs and one normally open
50mA PGM output (on SPC-ZX8 only).
Do not connect more than one Zone Expansion Module.
Bold
= Default Setting
PGM TIMER
(Zone Module SPC-ZX8 Only)
[655]
___/___/___seconds (000 = follow stop event)
PGM1
TIMER
(
HARDWIRE
)
5 sec. (default)
SECTION [650]: Options
Option
OFF
ON
[1]
EOL (end-of-line) Resistors for hardwire modules
l
No EOL
l
Use EOL Resistors
[2]
Zone Expansion Module Tamper Recognition
l
Disabled
l
Z1 becomes tamper input
[3]
PGM1 on Zone Expansion Module follows Global
PGM programmed in sections [124] & [125]
l
Disabled
l
Enabled
[4]
Future Use
l
N/A
l
N/A
[5]
Future Use
l
N/A
l
N/A
[6]
Future Use
l
N/A
l
N/A
[7]
Future Use
l
N/A
l
N/A
[8]
Future Use
l
N/A
l
N/A
SECTION [651]: Zone Assignment
Option
OFF
ON
[1]
l
Disabled
l
Z1 = Expan. Input 1 =
[2]
l
Disabled
l
Z2 = Expan. Input 2 =
[3]
l
Disabled
l
Z3 = Expan. Input 3 =
[4]
l
Disabled
l
Z4 = Expan. Input 4 =
[5]
l
Disabled
l
Z5 = Expan. Input 5 =
[6]
l
Disabled
l
Z6 = Expan. Input 6 =
[7]
l
Disabled
l
Z7 = Expan. Input 7 =
[8]
l
Disabled
l
Z8 = Expan. Input 8 =
WARNING!
Avoid assigning devices from different modules to the same Expansion Input. For example, do not assign a wireless trans-
mitter to section [601], then connect a detection device to Z1 of a hardwire module and enable option [1] in section [651].
This would mean both devices have been assigned to the same Expansion Input.