background image

  

 Spectra Series 

  29

USER OPERATION

TROUBLE DISPLAY 

The Spectra system continuously monitors fourteen possible trouble conditions. When a trouble condition occurs, the [

TBL

]

button or [

TRBL

] indicator will illuminate on the LED keypads or “Trouble” will appear on the LCD keypad’s screen. Press the

[

TBL

]

 or 

[

TRBL

]

 button to switch to the 

Trouble Display

. The 

[

TBL

]

 button or 

[

TRBL

]

 indicator will flash and lights corresponding

to an existing trouble condition will illuminate on the LED keypads (see below) or the appropriate trouble message will appear
on the LCD keypad. Press the 

[

CLEAR

]

 button to exit the 

Trouble Display

Please note that the keypad can be programmed to emit a “

BEEP

” every 5 seconds whenever a new trouble condition has

occurred. Pressing the 

[

TBL

]

 or 

[

TRBL

]

 button will stop the “beeping”.

LED #

Description

Details

[1]

No/Low Battery Failure

The control panel performs a dynamic battery test under load every 60 seconds. This trou-
ble indicates that the back-up battery is disconnected or that the battery should be 
replaced, as it will not provide adequate back-up current in case of AC loss. This trouble 
will also appear when the control panel is running on battery power and the battery voltage 
has dropped to 10.5 volts or lower. This means the battery must be recharged or replaced.

[2]

Wireless Transmitter 
Low Battery

This means the battery voltage of a 

Liberator

 wireless transmitter has dropped to 6.5V or 

less. Also, the yellow LED on the transmitter can flash to indicate this trouble. The bat-
tery should be replaced. 

[3]

Power Failure

Upon power failure, the AC LED on all keypads will turn off. The control panel can trans-
mit the report code programmed in section 

[205]

. This report code can be delayed by 

programming a Power Failure Report Delay in section 

[086]

. The AC LED turns back on 

as soon as power is restored.

[4]

Bell or PGM2 Disconnected

There is no bell or siren connected to the bell output terminals of the control panel or there 
is no device connected to the PGM2 terminals (1755, 1755EX, 1758 and 1758EX only). If 
you are not using the 

BELL

 or 

PGM

2 terminals, the trouble indicator will always be on. To 

avoid this, connect a 1K

 resistor across the bell or PGM2 output.

[5]

Maximum Bell Current

The 

BELL

 output uses a fuseless circuit and will automatically shut down if the current 

exceeds 3A  with a 1725, 1725EX, 1728, or 1728EX or 2.5A with a 1755, 1755EX, 1758, 
or 1758EX . After opening the short or reducing the load, the bell current is restored upon 
the following alarm generation. This trouble indicator will only appear when a condition has 
occured that would activate the bell output (e.g. during an alarm). 

[6]

Maximum Auxiliary Current

The auxiliary output uses a fuseless circuit to protect the power supply against current 
overload and automatically shuts down if the current exceeds 1.1A. After opening the 
short or reducing the load, the panel will restore power to the auxiliary output.

[7]

Communicator Report Fail

The control panel has failed all attempts to communicate with the central monitoring station.

[8]

Timer Loss

The control panel’s internal clock must be re-programmed. To re-program the timer press the 

[8]

 key and enter the current time using the 24-hour clock (i.e. 8:30PM = 20:30).

[9]

Tamper/Zone Wiring Fail

If the Tamper Recognition options are enabled, this trouble indicates a wiring problem on 
one or more zones or that the cover has been removed on one or more wireless transmit-
ters. In order to provide line short recognition the zone connections must have EOL resis-
tors. If you press the 

[9]

 key, the keypad will display which zones are in trouble.

[10]

Telephone Line Monitoring

If the Telephone Line Monitoring (TLM) feature is enabled (see section [135]), this trouble 
indicates that the control panel has not detected the presence of a telephone line for 30 sec.

[

STAY

OR

 [11]

Fire Loop Trouble

Denotes a wiring problem on zone 3, if defined as a Fire Zone.

[

FORCE

or [16]

Keypad Fault

If the keypad is no longer communicating with the control panel, the [

TBL

] or [

TRBL

] will 

flash, the [

FORCE

] key will illuminate (the LCD keypad displays “Keypad Fault”) and the 

keypad will emit four consecutive beeps at 5-second intervals. Press any key on the key-
pad to terminate the “beeping” sequence. When communication has been restored, the 
system will revert to previous status.

[

BYP

OR

 

[12]

Module Loss

A Liberator or zone module is no longer communicating with the control panel. 

[

MEM

OR

 

[13]

Wireless Transmitter 
Supervision Loss

One or more wireless transmitters are no longer communicating with the receiver. If you 
press the [

MEM

] key, the keypad will display which zones are in trouble. 

Summary of Contents for Spectra 1725

Page 1: ...PROGRAMMING GUIDE SPECTRA CONTROL PANELS V1 2 1725 1725EX 1728 AND 1728EX 1755 1755EX 1758 AND 1758EX...

Page 2: ......

Page 3: ...RT CODES 16 Arming Report Codes 16 Disarming Report Codes 16 Alarm Report Codes 17 Tamper Report Codes 17 System Trouble Report Codes 17 Programmable Ademco Contact ID Report Code List 18 All Codes Ad...

Page 4: ...ypass Recall Feature 33 One Touch Arming 33 Keyswitch Arming 33 Panic Alarms 33 Auto Arming 34 Alarm Memory Display 34 Programming Chime Zones 34 Keypad Muting 34 Quick Function Keys 34 HARDWARE CONNE...

Page 5: ...Spectra Series 3...

Page 6: ...ctions 001 to 016 127 to 138 302 to 348 610 650 to 651 After entering the programming mode as described in the shaded box above each option from 1 to 8 will represent a specific feature or option Pres...

Page 7: ...ote controls see page 28 Download to DESTINATION Control Panel 1 Remove AC and battery power from the control panel 2 Insert the Memory Key onto the serial connector labeled KEY on the Spectra control...

Page 8: ...odule or Z1 to Z8 of the SPC ZX8 module represent expansion inputs 1 to 8 respectively Please note that the module s inputs must be enabled in section 651 of the control panel Refer to Zone Assignment...

Page 9: ...____ ____ ____ 1 2 3 4 5 6 7 8 010 Zone 10 ____________________ ____ ____ 1 2 3 4 5 6 7 8 011 Zone 11 ____________________ ____ ____ 1 2 3 4 5 6 7 8 012 Zone 12 ____________________ ____ ____ 1 2 3 4...

Page 10: ...2 45 sec 071 ___ ___ ___ seconds EXIT DELAY 1 30 sec 072 ___ ___ ___ seconds EXIT DELAY 2 30 sec 073 ___ ___ ___ minutes 000 no bell on alarm BELL CUT OFF TIME PARTITION 1 4 min 074 ___ ___ ___ minute...

Page 11: ...6 Zones 1 to 16 99 Any Zone 02 Partition Status 00 System not ready Partition 1 only 01 System ready Partition 1 only 02 Steady Alarm in Partition 03 Pulsed Alarm in Partition 04 Pulsed or Steady Alar...

Page 12: ...to Close auto arming failed 02 No Movement Auto Arming 03 Partial Arming stay force instant bypass 04 One Touch Arming 05 Arm with WinLoad Software 06 Arm with Keyswitch 99 Any Sub Group 15 Disarm wi...

Page 13: ...re Partition 1 only 01 AC Loss restore Partition 1 only 02 Battery Failure restore Partition 1 only 03 Auxiliary current overload restore Partition 1 only 04 Bell current overload restore Partition 1...

Page 14: ...d 2 Tamper Supervision l Disabled l Enabled SECTION 129 General Options Option OFF ON 1 PGM2 Output Activation Option l Steady l Pulse flash 2 PGM2 Pulse Once Every 30sec If System Armed l Disabled l...

Page 15: ...s l No 8 Normal State of Global PGM l Normally Closed N C l Normally Open SECTION 132 Zone Options Option OFF ON 1 2 l see table l see table l see table l see table 3 Generate Tamper if detected on By...

Page 16: ...ure Use l N A l N A SECTION 136 Dialer Options Option OFF ON 1 Call Back l Disabled l Enabled 2 Automatic Event Buffer Transmission l Disabled l Enabled 3 Contact I D Report Codes l Programmable l All...

Page 17: ...__ __ __ __ __ __ __ __ CENTRAL STATION TELEPHONE OR PAGER NUMBER 1 32 DIGITS if less than 32 press ENTER to accept 152 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __...

Page 18: ...ode 37 __ __ Access code 38 __ __ Access code 39 __ __ Access code 40 170 __ __ Access code 41 __ __ Access code 42 __ __ Access code 43 __ __ Access code 44 171 __ __ Access code 45 __ __ Access code...

Page 19: ...12 200 __ __ Zone 13 __ __ Zone 14 __ __ Zone 15 __ __ Zone 16 RESTORE 201 __ __ Zone 1 __ __ Zone 2 __ __ Zone 3 __ __ Zone 4 202 __ __ Zone 5 __ __ Zone 6 __ __ Zone 7 __ __ Zone 8 203 __ __ Zone 9...

Page 20: ...m Peripheral 43 525 Reversing Relay Disable 70 134 Entry Exit 15 331 Polling Loop Open 44 SYSTEM PERIPHERAL DISABLES 530 540 135 Day Night 16 332 Polling Loop Short 45 COMMUNICATION DISABLES 550 560 1...

Page 21: ...n by user Disarm after alarm with Keyswitch 1 4A9 Keyswitch Open Auto Arming Cancellation 1 4A5 Deferred Open Close Disarm with PC software 1 4A7 Remote arm disarm Disarm after an alarm with PC softwa...

Page 22: ...Low Battery 3 384 RF xmtr low battery Wireless Transmitter Supervision Loss 3 381 Loss of super RF Module fault restore 3 333 Expansion module failure restore Printer fault restore 3 336 Local printe...

Page 23: ...ser Code 018 1 2 3 4 5 6 7 8 319 User Code 019 1 2 3 4 5 6 7 8 320 User Code 020 1 2 3 4 5 6 7 8 321 User Code 021 1 2 3 4 5 6 7 8 322 User Code 022 1 2 3 4 5 6 7 8 323 User Code 023 1 2 3 4 5 6 7 8 3...

Page 24: ..._EXPANSION INPUT 1 602 ___ ___ ___ ___ ___ ___EXPANSION INPUT 2 603 ___ ___ ___ ___ ___ ___EXPANSION INPUT 3 604 ___ ___ ___ ___ ___ ___EXPANSION INPUT 4 605 ___ ___ ___ ___ ___ ___EXPANSION INPUT 5 6...

Page 25: ...ts will appear one at a time by illuminating the corresponding light To view the next digit press the ENTER key On LCD keypads the entire serial number will appear on the screen STEP 4 Return to STEP...

Page 26: ...ng of 3 characters and up is acceptable Section Description 631 Display Signal Strength of Expansion Input 1 Section 601 632 Display Signal Strength of Expansion Input 2 Section 602 633 Display Signal...

Page 27: ...sion Module Tamper Recognition l Disabled l Z1 becomes tamper input 3 PGM1 on Zone Expansion Module follows Global PGM programmed in sections 124 125 l Disabled l Enabled 4 Future Use l N A l N A 5 Fu...

Page 28: ...vate 100mS after any of the above events have occurred if programmed RESET ZONE EXPANSION MODULE 660 PRESS ENTER TO CONFIRM WILL RESET THE ZONE MODULE S SECTIONS 650 TO 657 TO DEFAULT VALUES Event Gro...

Page 29: ...TE CONTROL 1 A B C D A B C D A C B D 712 ____ ____ ____ ____ ____ ____ ____ ____ REMOTE CONTROL 2 A B C D A B C D A C B D 713 ____ ____ ____ ____ ____ ____ ____ ____ REMOTE CONTROL 3 A B C D A B C D A...

Page 30: ...E CONTROL TWICE YOU WILL HEAR A CONFIRMATION BEEP REMOTE CONTROL 4 735 PRESS A BUTTON ON A REMOTE CONTROL TWICE YOU WILL HEAR A CONFIRMATION BEEP REMOTE CONTROL 5 736 PRESS A BUTTON ON A REMOTE CONTRO...

Page 31: ...Bell Current The BELL output uses a fuseless circuit and will automatically shut down if the current exceeds 3A with a 1725 1725EX 1728 or 1728EX or 2 5A with a 1755 1755EX 1758 or 1758EX After openin...

Page 32: ...ssigned to partition 1 Master Code 2 is permanently assigned to partition 2 except when partitioning is disabled Master Code 2 will be assigned to partition 1 and can be used to create modify or delet...

Page 33: ...d If you make a mistake the keypad will emit a REJECTION BEEP When you have correctly Stay Armed the system the appropriate ARM indication will appear and the Exit Delay will be initiated Stay Arming...

Page 34: ...emit a REJECTION BEEP When correctly Force Armed the appropriate ARM indication will appear and the Exit Delay will be initiated Please note that Force Arming can also be activated using One Touch Fo...

Page 35: ...ress and hold the ENTER button for 3 seconds The system will switch to Exit Delay mode At the end of the Exit Delay period the control panel will switch to Regular Arming To Exit and Force Arm Press a...

Page 36: ...on Enter the 2 digit 01 to 16 zone number s When the corresponding LED is on the zone is chimed When the corresponding LED is off the zone is unchimed When the desired zones are chimed press ENTER LCD...

Page 37: ...Spectra Series 35 HARDWARE CONNECTIONS SINGLE ZONE INPUTS DOUBLE ZONE INPUTS with ATZ option only...

Page 38: ...36 Programming Guide CONNECTING A KEYSWITCH CONNECTING FIRE CIRCUITS PGM CONNECTIONS...

Page 39: ...Spectra Series 37 CONNECTING A LIBERATOR WIRELESS BUS MODULE SPC 319 CONNECTING A ZONE EXPANSION MODULE SPC ZX8...

Page 40: ...38 Programming Guide SPECTRA 1725 1725EX 1728 AND 1728EX PCB LAYOUT...

Page 41: ...river Option Only An optional siren driver is available with the Spectra 1755 1755EX 1758 and 1758EX control panels This siren driver allows you to connect speakers directly to the bell output as show...

Page 42: ......

Reviews: