IM728-738
The "late to close/no movement" code programmed at address 190 (SECTION 32) will be transmitted;
• at the time programmed at addresses 245 and 246 if the system is not armed (Late to Close).
• after the time programmed at address 253 expires (No Movement).
The amount of time programmed at address 254 (Max = 127 minutes) can be used to:
• designate the length of time a programmable output (PGM) will remain active following a specified
event.
Auto arm/report options
1) Report the code programmed at address 175 after the number of days programmed at address 244.
(To disable, program 000 at address 244.)
2) Send a "late to close" code programmed at address 190.
3) Auto arm the system (on time) if enabled at address 206, key [5].
Exit delay
(Address 247)
Range 001 to 255 seconds (
factory default 060 seconds). Applies to all zones upon arming.
Entry delay 1
(Address 248)
Range 001 to 255 seconds (
factory default 045 seconds). Applies upon entry to all zones not selected at
addresses 220 to 232.
Entry delay 2
(Address 249)
Range 001 to 255 seconds (
factory default 045 seconds). Applies to all zones selected at address 232,
upon entry.
Bell cut-off time
(Address 250)
Range 001 to 255 minutes (
factory default 005 minutes).
Zone speed
(Address 251)
Range 001 to 255 X 15mSec., (
factory default 600 mSec). Maximum time 3.8 seconds.
Power failure report delay
(Address 252)
Range 001 to 255 minutes, (
factory default 030 minutes), (000 = disabled). Delay code reported at
address 171.
Time for "no movement" report
(Address 253)
Range 001 to 255 X 15 minutes, (
factory default 8 hours), (000 = disabled). System will automatically
arm after programmed number of minutes of inactivity if enabled at address 206, key [6], or will transmit
code programmed at address 190. (Maximum time 63.75 hours)
PGM timer setting
(Address 254)
Range 001 to 127 seconds or 128 (1 minute) to 255 (127 minutes) (add number of minutes to 128;
i.e. For 5 minutes = 128 + 5 = 133
For 127 minutes = 128 + 127 = 255
Applies to PGM 1 and 2 if selected at address 195. (Maximum time, 127 minutes)
Installer Lock
(Address 255)
If 147 is programmed at address 255, all programming will be locked and will not be affected when the
system is reset.
“Power-down” reset
(1) Remove battery and AC to power down the unit.
(4) Wait 3 seconds.
(2) Connect a jumper between "reset jumper" pins.
(5) Remove jumper.
(3) Connect AC and/or battery.
Factory default installer and master codes will be reinstated. Values entered at addresses 059 - 243, as well
as all user codes, will be erased ([2
ND
] [2
ND
]). Programmed values of all other addresses do not change.
23