SMARTZONE G6 IRUPS USER MANUAL
6
7. Route cables to eliminate tripping hazards.
8. Do not connect domestic appliances such as hair dryers to UPS output.
9. Connect the UPS system only to an earth grounded outlet that is easily accessible
and close to the UPS system.
10. Use only UL, VDE, CE certified power cables to connect the UPS system to the
building wiring source (Mains).
11. Use only UL, VDE, CE certified power cables to connect the loads to the UPS system.
12. When installing the equipment, ensure that the sum of the leakage current of the UPS
and the connected devices does not exceed 3.5mA.
13. This product should be installed in an area with an altitude of less than 1000m. In
places over 1000m, the unit must be derate 1% for every 100 meters above 1000m.
This is an example of power derating according to altitude:
Altitude
(m)
1000
2000
2500
3000
3500
4000
4500
5000
Load
coefficient
100%
90%
85%
80%
75%
70%
65%
60%
14. The UPS cooling is depending on fans, so it should be kept in good air ventilation
area. There are many ventilation holes on the front and rear, so they should not be
blocked by any exotic obstacles.
15. Batteries should be mounted in an environment where the temperature is within the
required specs. Temperature is a major factor in determining battery life and capacity.
In a normal installation, the battery temperature is maintained between 15°C and
25°C. Keep batteries away from heat sources or main air ventilation area, etc.
16. Units with internal battery cartridges and battery cartridges must be stored in an
environment to protect against excessive humidity and heat source.
o
Typical battery performance is based on an operating temperature
between 20°C and 25°C. Operating the battery cartridges above this
range will reduce the battery life, while operating below this range will
reduce the battery capacity.
o
An unused battery cartridge must be fully recharged every 6 months.
Operation
17. Do not disconnect the input (Mains) cable on the UPS system or the building wiring
source, thus removing protective earth of the UPS system and of all connected loads,
during operation.
18. The UPS system features its own, internal power source (batteries). The UPS output
may be electrically live even if the UPS system input is not connected to the building
source.
19. To fully disconnect the UPS system, first press the OFF/Enter button then disconnect
the input source (Mains).
20.
Prevent fluids or other foreign objects from entering the UPS system.