SMARTZONE G6 IRUPS USER MANUAL
45
104.
If primary loads are non-linear loads, increase the cross-sectional areas of
neutral wires1.5
–1.7 times.
105.
106.
After completing the wiring, confirm again that all wiring is correct.
107.
Leave the terminal block cover off the rear panel for the next step of connecting
the EBP.
Recommended Cross-sectional Areas of Power Cables for Single Feed (same
source is connected to the UPS Input and Bypass)
SKU
Wiring
Number
of
Phases
Voltage
Current
Full Load***
(maximum)
External Input
Circuit Breaker
(typical)
Wire Size*
(typical)
U10N32V
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
26.9 A each phase
45.5 A
100 A**
not required
25 mm
2
**
16 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
26.9 A each phase
15.2 A each phase
40 A each phase
not required
10 mm
2
6 mm
2
U15N32V
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
34.9 A each phase
68.2 A
100 A**
not required
25 mm
2
**
16 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
34.9 A each phase
22.8 A each phase
40 A each phase
not required
10 mm
2
6 mm
2
U20N32V
Input
Output
3
1
380/400/415 VAC
220/230/240 VAC
42.9 A each phase
90.9 A
125 A**
not required
35 mm
2
**
25 mm
2
Input
Output
3
3
380/400/415 VAC
380/400/415 VAC
42.9 A each phase
30.4 A each phase
50 A each phase
not required
16 mm
2
10 mm
2
Recommended Cross-sectional Areas of Power Cables for Dual Feed (one
source is connected to the UPS Input and a different source is connect to the
UPS Bypass)
SKU
Wiring
Numb
er
Voltage
Current
Full
Load***
External
Input
Circuit
External Input
Circuit
Wire
Size
Mains*
Wire
Size
Bypass*