SMARTZONE G6 IRUPS USER MANUAL
44
83. These UPS units will have input hardwire connections.
84. Ensure that there is no power on the input wires, use lock-out tag-out at the breaker
panel. Refer to one of the tables below for the input breaker(s) and input power
cable(s) to be used based on the configuration of the UPS unit being deployed. The
breakers and cables must conform to the local wiring code according to environmental
conditions (temperature and natural conditions). NOTE: Each part of the system must
maintain a connected earth ground.
85. Remove the protective cover of the terminal block on the back of the UPS and retain
the screws and cover.
86. Crimp the provided ring terminals onto each wire with a standard crimping tool, for the
wire specified in the table below.
87. Connect each wire under the appropriate screw as indicated on the back of the UPS
(see the appropriate diagram in Figure 58). NOTE: Each part of the system must
maintain a connected earth ground.
88. If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415
V, multiply the currents by 0.92.
89. When the mains input and bypass input have the same input power source, configure
both types of input power cables as mains input power cables. The cables listed in
Table are used only when the following requirements are met:
90. Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E).
91. The ambient temperature is 30°C.
92. The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
93. 90°C copper flexible cable.
94. The length of the AC power cables are no longer than 30 m and DC power cables are
no longer than 50 m.
95. After completing the wiring, confirm again that all wiring is correct.
96. Leave the terminal block cover off the rear panel for the next step of connecting the
load(s).
97. Connect the load(s) to the UPS:
98. These UPS units have output hardwire connections.
99. Refer to one of the tables below for the output power cable to be used based on the
configuration of the UPS unit being deployed. The cable must conform to the local
wiring code according to environmental conditions (temperature and natural
conditions). NOTE: Each part of the system must maintain a connected earth ground.
100.
The protective cover on the terminal block should already be removed f rom the
last step.
101.
Crimp the provided ring terminals onto each wire with a standard crimping tool,
for the wire specified in the table below.
102.
Connect each wire under the appropriate screw as indicated on the back of the
UPS (see the appropriate diagram in Figure 58). NOTE: Each part of the system must
maintain a connected earth ground.
103.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is
415 V, multiply the currents by 0.92.