Functions
Panasonic ST4 Instruction Manual
66
4. The total time of the reset waiting time and the override execute time is the
override valid time. The override function will not be performed until the reset
waiting time is passed and the override conditions are met.
Emission halt
input (Note 1)
Override input
(Note 1)
Open
0V/+V
0V/+V
ON
OFF
ON
OFF
3 to 4 sec. (Note 2)
ON
Auxiliary output 2
(AUX 2)
OFF
ON
OFF
Within 1 sec.
25ms or less
Muting lamp
output
Control output
(OSSD 1 / 2)
Emission
condition
Sensor A / A’
Sensor B / B’
Absent
Present
Emission
Emission
halt
ON
OFF
Open
Override valid time (Note 3)
Override execute time
40ms or more
40ms or more
90ms or less
Sensing object
(Within the
protective area)
Time chart for auto-reset
NOTE
1. The order in which the emission halt input is opened and the override input
is short-circuited is not important.
2. This behavior is true when the muting lamp diagnosis function is active. If
the muting lamp does not light up after 4 seconds, the override function will
be deactivated. When the muting lamp diagnosis function is not active, the
muting function becomes active 3 seconds after the input conditions of the
muting sensor A (A') and
B (B') are satisfied. For the setting of the muting
lamp diagnosis function, refer to Muting Lamp Diagnosis Function (see page
74).
3. Override time can be set to either 60 or 600 seconds. For the setting, refer to
Muting Pattern Selection Function (see page 67).