188
11.14.10 REGARDING LOCAL SETTINGS
■
Local setting method using the remote controller
•
The settings can be performed at night with low sound by using the remote controller.
Follow the instructions below regarding installation, service and repair, and perform local setting.
(If there is a mistake with the settings, it will cause abnormal operations.)
•
Perform the local settings according to the installation instruction manual provided with the remote controller.
•
Mode number, setting values
Mode number
Item
Setting value
Setting content
000
No setting (Cancel)
001
Low sound level 1
002
Low sound level 2
02
Low sound at night
003
Low sound level 3
■
Model setting for cooling via a jumper wire
•
The unit designed for cooling can be set by the JP wire on the outdoor unit’s control
board.
[Setting method]
After disconnecting JP1 (COOL ONLY) as shown in diagram 1 while the power
supply has been turned OFF, switch the unit’s power supply back to ON.
By setting it to cooling operation, the heating operation cannot be used.
Once the unit is in cooling operation and in order to return to heating/cooling mode,
turn off the power supply. Disconnect JP1 and switch ON the power supply.
Note: Ensure to turn OFF the power supply before disconnecting JP1. There is a risk
of damaging the P board by disconnecting JP1 while the power supply is
turned ON.
11.14.11 CHECKS AFTER INSTALLATION HAVE COMPLETED
•
Check the following items after completing installation.
11.14.12 REGARDING DELIVERY TO THE CUSTOMER
•
Request the customer to review the instruction manual and explain the operating method for the product.
•
During delivery, not only provide explanation of the operating methods but the serviceperson also writes his/her
name in the comment column (back page of the instruction manual) and gives it to the customer. In addition, it is
also recommended that regular inspection checks are agreed upon for maintenance.
Refer to the installation instruction manual provided with the indoor unit for the specifications on the indoor
unit installation.
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...