84
Note
●
Thoroughly study the following installation locations
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the
fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
•
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that
it draws oily steam which should not flow into the suction of the air conditioner.
•
Make enough distance from the cooking room to install the air conditioner in such place where it may not
suck in oily steam.
Cooking table
Ensure ample
distance
Use the ventilation fan for smoke-
collection hood with sufficient capacity.
2. Avoid installing the air conditioner in such circumstances where cutting oil mist or iron powder exist
especially in factories, etc.
3. Avoid places where inflammable gas is generated, flows-in, contaminated, or leaked.
4. Avoid places where sulphurous acid gas or corrosive gas can be generated.
5. Avoid places near high frequency generators.
11.4.3
INSTALLATION OF INDOOR UNIT
HOW TO FIX INSTALLATION PLATE
The mounting wall shall be strong and solid enough to prevent it from the vibration.
128
Wall
Wall
Wall
Installation
plate 1
2 screw
More than
Measuring
Tape
Indoor unit
241.5mm
128 mm
234.5 mm
128 mm
More
than
1
5
6
A
B
C
4
3
More than
1
2
Dimension
Model
○
1
○
2
○
3
○
4
○
5
○
6
S-22KA**, S-28KA**
S-36KA**, S-45KA**
535 mm
82 mm
165 mm
158 mm
43 mm
95 mm
S-56KA**, S-63KA**
S-71KA**
635 mm
82 mm
165 mm
158 mm
169 mm
219 mm
The centre of installation plate should be at more than
○
1 at right and left of the wall.
The distance from installation plate edge to ceiling should more than
○
2 .
From installation plate left edge to unit’s left side is
○
3 .
From installation plate right edge to unit’s right side is
○
4 .
○
B
: For left side piping, piping connection for liquid should be about
○
5 from this line.
: For left side piping, piping connection for gas should be about
○
6 from this line.
1. Mount the installation plate on the wall with 5 screws or more (at least 5 screws).
(If mounting the unit on the wall, consider using anchor bolts.)
•
Always mount the installation plate horizontally by aligning the marking-off line with the thread and using a
level gauge.
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...