LOW SOUND NIGHT MODE SETTING
○
1
Perform the steps (1) through (5) from the local setting procedure.
For step (2), select “02”.
For step (4), select from “001”, “002” or “003”.
○
2
Press the MODE (TIMER) switch to display the “start” time for low sound night mode.
○
3
Use the UP / DOWN (TIMER) switches to set the start time for low sound night mode.
○
4
Press the SELECT switch to display the “end” time for low sound night mode.
○
5
Use the UP / DOWN (TIMER) switches to set the end time for low sound night mode.
○
6
The start and end time for low sound night mode is fixed with the SET switch.
i
After checking the settings, press the TEST RUN switch to return to the normal display.
Note: Be sure to always set the current time with the wired controller.
(Refer to the instruction manual for the current time setting method)
For automatic address resetting for group control, switching the thermistor, and ventilation unit control, set and
choose the mode number and corresponding value in the table according to the local setting procedure.
IF REMOTE CONTROLLER DISPLAYS NOTHING
•
Check the power supply to the indoor unit.
•
Check once more that the remote control cable is securely connected.
(Check for loose terminals, poor contacts, connection positions on the terminal block, etc.)
•
If the above checks show that nothing is wrong but nothing still appears on the remote controller display, refer to
“Settings” in the installation manual that is provided with the indoor unit.
SETTING FOR 1 REMOTE CONTROLLER GROUP CONTROL
•
A maximum of 16 indoor units can be connected at the time of group control. (Do not connect the heat pump unit
with the cooling only unit.)
•
There are 2 methods for setting the group control address (A/C No.); an automatic and a manual setting method.
•
The A/C No. setting cannot be confirmed when using the automatic method.
•
To set each indoor unit’s A/C No., use the manual setting method.
However, if the wall type indoor unit is connected, then manual setting is not possible.
■
Automatic setting
•
By switching ON the indoor unit’s power supply with the DIP switch where the A/C No. is set to “01” (factory
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic
setting takes approximately one minute.)
•
Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored.
To reset the A/C No. setting, follow the instructions for the “group control automatic address reset”. Refer to
the item “Local setting” in the installation instruction manual that comes with the wired controller for the
“group control automatic address reset” method.
* If the indoor unit’s A/C No. DIP switch is not set to “01”, the automatic setting cannot be reset.
■
Manual setting
•
The manual setting is performed using each indoor unit’s printed circuit board DIP switch. (Refer to the
diagram below)
•
Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is
turned ON, the stored A/C No. is recalled.
•
To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch.
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control.
* Ensure to set the A/C No. to “01” for 1 indoor unit.
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...