101
11.5.10 AS FOR TIMER OUTPUT
•
Connect the timer cord to connector (CN-TIMER) on print circuit board.
Printed
circuit
board
Timer
Contact
Close: RUN
Open: STOP
d.c. 5V
CN-TIMER
2
1
Relay contact
Connector
Timer setting
•
The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd.
•
Wiring must use vinyl code with the sheath or cable line diameter 0.3mm
2
.
•
The length of wiring should be within 150m and separated from power line in order to prevent malfunction.
•
The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current
suitable for this.
11.5.11 PRECAUTION IN TEST RUN
For test run, refer to the “Precautions in test run” in the outdoor unit installation instructions manual.
Test run is conducted using the wired controller, emergency switch on the infrared receiver or by using the outdoor
units. For the wired controller test run see the instructions below.
TEST RUN
•
Switch the power supply to ON for at least 12 hours in advance before the test run.
•
First, press the ON/OFF ( ) button.
•
Next, select the operational modes.
•
Then press the TEST RUN button within 1 minute of pressing the ON/OFF ( ) button.
•
Be sure to run the cooling operation test run for at least 20 minutes before starting the heating
operation test run.
•
Press TEST RUN or ON/OFF ( ) button again to cancel the test run mode.
NOTE 1
Detaching a connector with electrical current may cause damage to the control board. Ensure to
turn OFF the power supply and wait for at least 5 minutes before performing this operation.
NOTE 2
Do not short the remote control wires. (There is no protective circuit operation.) Normal operation
will commence once the short is solved.
NOTE 3
During the test run; ensure to operate the units in cooling mode prior to operating the units in
heating mode. Caution: Operating the units in heating mode first may cause compressor failure.
NOTE 4
Test run should be performed for a minimum of 20 minutes. (Test run using the remote controller
will change to normal operation after 30 minutes.)
NOTE 5
Use the outdoor unit to cancel the outdoor unit test run and the wired controller to cancel the wired
controller test run. For the test run method using the AUTO button on the infrared receiver, refer to
the “Emergency operation” section in the installation instruction manual for the infrared receiver.
11.5.12 CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
•
After completing work, be sure to measure and record trial run properties, and store measuring data, etc.
•
Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind
velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping
temperature.
•
As to the structure and appearance, check the following items.
Is circulation of air adequate?
Is draining smooth?
Is heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is remote controller switch operated?
Is there any faulty wiring?
Are the terminal screws loosened?
M3…69-98N•cm {7-10kgf•cm}
M4…157-196N•cm {16-20kgf•cm}
M5…196-245N•cm {20-25kgf•cm}
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...