140
11.11.4 SETTINGS
CONTROL USING TWO REMOTE CONTROLLERS
•
If both the infrared remote controller and the optional wired remote controller are being used together, either
remote controller can be used to operate the indoor units. (The indoor unit can be used to operated with the last
switch pressed having priority.)
•
Up to 2 optional wired remote controllers can be connected and used.
1 REMOTE CONTROLLER GROUP CONTROL
•
When using group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units
and cooling only units.)
•
For details on how to set the address (A/C No.) for group control, refer to the “Setting for 1 remote controller
group control” section in the installation instructions provided with the indoor unit.
Wired
control
(optional)
Indoor unit No. 1
Indoor unit No. 2
Indoor unit No. 3
DIP
switch
DIP
switch
DIP
switch
Printed
circuit
board
Printed
circuit
board
Printed
circuit
board
Terminal
block
Terminal
block
Terminal
block
Infrared receiver
LOCAL SETTING
•
Press the SET switch
○
2 to operate the “Local setting mode”.
•
Use
the switches TEMP to choose the “Mode No.”
•
Use
the switches TIMER to choose the “Setting value”.
•
Press the SET switch
○
1 to check the setting details.
The setting details are displayed for approximately 4 seconds and then
it exits the local setting mode.
If no operation is performed, the “Local setting mode” clears after 30 seconds.
Model No.
Item
Setting Value
Setting Remarks
000 Clear
address
00
Indoor unit address setting
001 ~ 200
Set address
“001” to “200”
000
Not set (Clear)
001
Low sound level 1
002
Low sound level 2
02
Low sound at night
003
Low sound level 3
000 Clear
address
06
Outdoor unit address setting
001 ~ 199
Set address
“001” to “199”
Note: 1. The default setting at shipment is “000”.
SETTING INDOOR UNIT ADDRESS
•
Setting and clearing the indoor unit address (Central control address) can be performed.
•
It is possible to set the address value from “001” to “200”. Setting the address to “000” clears it.
•
Set the mode number to “00” and choose a setting value from “000” to “200” according to the local setting
procedure.
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...