133
■
Automatic setting
•
By switching ON the indoor unit’s power supply with the DIP switch where the A/C No. is set to “01” (factory
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic
setting takes approximately one minute.)
•
Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored.
To view the resetting result, follow the instructions for the “group control automatic address reset”. Refer to
the item “On-site setting” in the installation instruction manual that comes with the wired controller for the
“group control automatic address reset” method.
* If the indoor unit’s A/C No. DIP switch is not set to “01”, the automatic setting cannot be reset.
■
Manual setting
•
The manual setting is performed using each indoor unit’s printed circuit board DIP switch. (Refer to the
diagram below)
•
Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is
turned ON, the stored A/C No. is recalled.
•
To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch.
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control.
* Ensure to set the A/C No. to “01” for 1 indoor unit.
A/C No.
01
02
03
04
05
06
07
08
Indoor unit
printed circuit
board DIP switch
(SW2)
Unnecessary
operation
1-ON
2-ON
1,2-ON
3-ON
1,3-ON
2,3-ON
1,2,3-ON
A/C No.
09
10
11
12
13
14
15
16
Indoor unit printed
circuit board DIP
switch (SW2)
4-ON
1,4-ON
2,4-ON
1,2,4-ON
3,4-ON
1,3,4-ON
2,3,4-ON
1,2,3,4-ON
(Refer to the remote controller’s installation instruction manual for the remote controller settings.)
11.9.9
AS FOR TIMER OUTPUT
•
Connect the timer cord to connector (CN-TIMER) on print circuit board.
Printed
circuit
board
Timer
Contact
Close: RUN
Open: STOP
d.c. 5V
CN-TIMER
2
1
Relay contact
Connector
Timer setting
•
The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd.
•
Wiring must use vinyl code with the sheath or cable line diameter 0.3mm
2
.
•
The length of wiring should be within 150m and separated from power line in order to prevent malfunction.
•
The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current
suitable for this.
Summary of Contents for S-32NA1E5
Page 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Page 12: ...12 ...
Page 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Page 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Page 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Page 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Page 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Page 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Page 58: ...58 ...
Page 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Page 60: ...60 ...
Page 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Page 62: ...62 ...
Page 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Page 64: ...64 ...
Page 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Page 66: ...66 ...
Page 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Page 68: ...68 ...
Page 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Page 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Page 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Page 195: ...195 ...
Page 201: ...201 ...