54
Data register
Name
Unit
Kind of data
Range
R/W
DT31925
Max. demand date
current1
-
Unsigned
16bit
Higher Lower
yy:00H to 99H, mm:01H to 12H
R
DT31926
Max. demand time
current1
-
Unsigned
16bit
Higher Lower
dd:01H to 31H, hh:00H to 23H
R
DT31927
Max. demand time
current1
-
Unsigned
16bit
Higher Lower
min,:00H to 59H, ss:00H to 59H
R
DT31928
Max. demand value
current1
0.001A
Unsigned
32bit
0 to 999999999
R
DT31929
DT31930
Max. demand date
current2
-
Unsigned
16bit
Higher Lower
yy:00H to 99H, mm:01H to 12H
R
DT31931
Max. demand time
current2
-
Unsigned
16bit
Higher Lower
dd:01H to 31H, hh:00H to 23H
R
DT31932
Max. demand time
current2
-
Unsigned
16bit
Higher Lower
min,:00H to 59H, ss:00H to 59H
R
DT31933
Max. demand value
current2
0.001A
Unsigned
32bit
0 to 999999999
R
DT31934
DT31935
Max. demand date
current3
-
Unsigned
16bit
Higher Lower
yy:00H to 99H, mm:01H to 12H
R
DT31936
Max. demand time
current3
-
Unsigned
16bit
Higher Lower
dd:01H to 31H, hh:00H to 23H
R
DT31937
Max. demand time
current3
-
Unsigned
16bit
Higher Lower
min,:00H to 59H, ss:00H to 59H
R
DT31938
Max. demand value
current3
0.001A
Unsigned
32bit
0 to 999999999
R
DT31939
* ’Range’ is not the measurement range, it shows the data range.
Note1) R: Read W: Write
2) Data register except specified is 0.
3) If each setting value is wrote by communication, it memories to internal memory at the same
time. Therefore, change setting frequently makes the internal memory’s life short. Avoid to
usage like this.
4) Write a data within the range when you write it.