127
Data identification
Name
Data
format
unit
byte
range
R/W
DI
3
DI
2
DI
1
DI
0
04 05 02
06 Unit for pulse output
OUT1
XXX
-
2
1(0.0001kWh),
2(0.001kWh), 3(0.01kWh)
4(0.1kWh), 5(1kWh),
6(10kWh), 7(100kWh)
100(Stand-by alarm)
101(Under voltage alarm)
102(Over voltage alarm)
103(Power interruption alarm)
104(Current alarm)
105(Active power alarm)
106(Count output 1)
107(Count output 2)
108(Level output )
109(PF alarm)
110(Current harmonics alarm)
111(Voltage harmonics alarm)
112(Current THD alarm)
113(Voltage THD alarm)
114(Current unbalancing alarm)
115(Voltage unbalancing alarm)
116(Under current alarm)
117(Reactive power alarm)
118(Apparent power alarm)
119(Over frequency alarm)
120(Under frequency alarm)
121(Power demand alarm)
122(Current demand alarm)
R/W
07 Unit for pulse output
OUT2
XXX
-
2
1(0.0001kWh),
2(0.001kWh), 3(0.01kWh)
4(0.1kWh), 5(1kWh),
6(10kWh), 7(100kWh)
100(Stand-by alarm)
101(Under voltage larm)
102(Over voltage alarm)
103(Power interruption alarm)
104(Current alarm)
105(Active power alarm)
106(Count output 1)
107(Count output 2)
108(Level output )
109(PF alarm)
110(Current harmonics alarm)
111(Voltage harmonics alarm)
112(Current THD alarm)
113(Voltage THD alarm)
114(Current unbalancing alarm)
115(Voltage unbalancing alarm)
116(Under current alarm)
117(Reactive power alarm)
118(Apparent power alarm)
119(Over frequency alarm)
120(Under frequency alarm)
121(Power demand alarm)
122(Current demand alarm)
R/W
08
Integral power output
target phase
OUT1
X
-
1
1:Phase1, 2:Phase2,
3:Phase3,
5:total
R/W
09
Integral power output
target phase
OUT2
X
-
1
1:Phase1, 2:Phase2,
3:Phase3,
5:total
R/W