130
Data identification
Name
Data
format
unit
byte
range
R/W
DI
3
DI
2
DI
1
DI
0
04 05 02
41 Voltage THD alarm
(phase) OUT2
X
-
1
0:All,1:Phase1(line1-2),
2:Phase2(line2-3),
3:Phase3(line3-1)
R/W
42 Under current alarm
(phase) OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
43 Under current alarm
(phase) OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W
44
Current unbalancing
alarm(ON threshold)
OUT1
XXX.XX
0.01%
3
0 to 99999
R/W
45
Current unbalancing
alarm(OFF threshold)
OUT1
XXX.XX
0.01%
3
0 to 99999
R/W
46
Current unbalancing
alarm(ON threshold)
OUT2
XXX.XX
0.01%
3
0 to 99999
R/W
47
Current unbalancing
alarm(OFF threshold)
OUT2
XXX.XX
0.01%
3
0 to 99999
R/W
48
Voltage unbalancing
alarm(ON threshold)
OUT1
XXX.XX
0.01%
3
0 to 99999
R/W
49
Voltage unbalancing
alarm(OFF threshold)
OUT1
XXX.XX
0.01%
3
0 to 99999
R/W
4A
Voltage unbalancing
alarm(ON threshold)
OUT2
XXX.XX
0.01%
3
0 to 99999
R/W
4B
Voltage unbalancing
alarm(OFF threshold)
OUT2
XXX.XX
0.01%
3
0 to 99999
R/W
4C Reactive power alarm
(ON threshold) OUT1
XXXXXXX.X 0.1kvar
4
0 to 29999999
R/W
4D Reactive power alarm
(OFF threshold) OUT1
XXXXXXX.X 0.1kvar
4
0 to 29999999
R/W
4E Reactive power
alarm(phase)OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3,5:total R/W
4F Reactive power alarm
(ON threshold) OUT2
XXXXXXX.X 0.1kvar
4
0 to 29999999
R/W
50 Reactive power alarm
(OFF threshold) OUT2
XXXXXXX.X 0.1kvar
4
0 to 29999999
R/W
51 Reactive power alarm
(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3,5:total R/W
52 Apparent power alarm
(ON threshold) OUT1
XXXXXXX.X 0.1kVA
4
0 to 29999999
R/W
53 Apparent power alarm
(OFF threshold) OUT1
XXXXXXX.X 0.1kVA
4
0 to 29999999
R/W
54 Apparent power alarm
(phase)OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3,5:total R/W
55 Apparent power alarm
(ON threshold) OUT2
XXXXXXX.X 0.1kVA
4
0 to 29999999
R/W
56 Apparent power alarm
(OFF threshold) OUT2
XXXXXXX.X 0.1kVA
4
0 to 29999999
R/W
57 Apparent power alarm
(phase)OUT2
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3,5:total R/W
58 Over frequency alarm
(ON threshold) OUT1
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
59 Over frequency alarm
(OFF threshold)OUT1
XXX.XX
0.01Hz
3
0.01 to 100.00
R/W
5A Over frequency alarm
(phase)OUT1
X
-
1
0:All,1:Phase1,
2:Phase2,3:Phase3
R/W