125
Reset integral power
It reset all integral power.
For reset integral power, workers code should be designated, but it doesn’t record and the code is
fixed to ‘0’. It is available only with pressing <MODE> key (programming key).
・
Command from master; control code 1AH
68H A0 A1 A2 A3 A4 A5
68H
1AH
08H
⇒
continue
Transmission address
Control code
⇒
continue
PA
P0
P1
P2
⇒
continue
Authorization level (33H fix)
Password (P2: 33H fix)
⇒
continue
C0
C1
C2
C3
CS 16H
Workers code (33H fix)
・
Response from slave (normal)
68H
A0
A1
A2
A3
A4
A5
68H 9AH 00H
CS
16H
Abnormal command from slave
Control code (C); C0H (Response from slave is abnormal.)
+ Control code when error occurs.
68H A0
A1
A2
A3
A4
A5 68H
C
01H
ERR
16H
Control code
Error code
(bit flag)
Contents of
error code
Bit flag
Contents
Bit 7
Not support
Bit 6
Not support
Bit 5
Not support
Bit 4
Not support
Bit 3
Impossible to change transmission speed
Bit 2
Password mistake
Bit 1
No request data
Bit 0
Other errors
Conditions for no response
With the below conditions, slave doesn’t response.
・
Parity error
・
CS error
・
Data length (L) doesn’t match byte count.
・
Error at write or read of transmission address
・
Not press programming key (<MODE> key)
Programming key
Programming key is <MODE> key.
With every display, it is possible to change the settings only when pressing <MODE> key.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]